EASYLOGO 2-00 E
B 55002.11-2022.01
PRODUCT DESCRIPTION
1
Housing
8
Connection for high water level sensor (pre-assembled)
2
Fixing lug
9
Connection for potential-free changeover contact
3
“Fault” indicator
10
Pump 2 (P2) socket
4
“High water alarm” indicator
11
Pump 1 (P1) socket
5
“Pump 1” indicator
12
High water alarm “acknowledge” button
6
“Pump 2” indicator
13
Mains power connection
7
High water level sensor
Electronic control unit for switching two direct starting pumps on and off, depending on the level, using built-in level control monitoring.
After each pumping cycle, the order in which pump 1 (P1) and pump 2 (P2) are switched on is changed.
In the event of a high water level, the switched-off pump is turned on in addition to the other pump.
In the event of a fault, the switched-off pump is turned on so that the wastewater can continue to be pumped out.
Faults are signalled via a red LED that is dependent on mains power.
The pre-assembled high-water level sensor is attached to the guide rail system. In the event of a high water level, this triggers an alarm
which is signalled via a yellow LED and the alarm buzzer.
Options
∙
Built-in potential-free changeover contact to relay high-water alarm.
∙
The control unit can be fitted with a 9V NiMh battery. The high water alarm is maintained in the event of a power outage. The battery
capacity is sufficient for a continuous alarm of about 1 hour.
ENGLISH
12