Summary of Contents for Hydromatic H-03-000

Page 1: ...you provide this manual to the owner of the equip ment or to the responsible party who maintains the system STANDARD ELECTRICAL CONTROL PANEL INSTALLATION AND SERVICE MANUAL Item H 03 000 Part 5625 000 1 2012 Pentair Pump Group Inc 10 31 12 ...

Page 2: ... the terminal block con nec tions CAUTION Nonmetallic enclosures do not provide grounding conduit con nec tions Use grounding bush ing and jumper wires Make the Following Electrical Con nec tions a Connect the pump leads to the control panel If pump is single phase and the panel has start ca pac i tor start relay and run ca pac i tor it is critical that the pump leads be connected prop er ly The W...

Page 3: ...reak er is not a switch ing device Excessive operations tend to affect the trip curve of the breaker 2 Check contactors and relays for excessive humming This can be accomplished by turning pumps on and off in the Hand mode with the H O A switch 3 Check pump run light s by run ning pump s in Hand mode Check bulb s in any other light s 4 With the power off check con ti nu ity of all control fuses 5 ...

Page 4: ...panel It should agree with the sche mat ic f Check contactor coil re sis tance 2 Pump does not run in Auto position a Check items a through f per Item 1 above b Floats may be miswired to control panel Check float type N O or N C and hook up by re fer ring to the schematic If the start and stop floats are hooked in reverse pump will short cycle and will not pump the level down c Check pump controll...

Page 5: ...perage of each lead 5 Move each lead to the next terminal 1 to 3 2 to 1 3 to 2 6 Againreadtheamperage of each lead 7 If the unbalance moves with the motor leads the un bal ance is caused by the mo tor If the unbalance remains with the terminals the unbal ance is in the pow er supply 8 If the current unbalance exceeds five percent nui sance tripping or ex ces sive heating will result 9 Connect lead...

Page 6: ...ad current during starting f After the motor has started within one sec ond the cur rent should drop to a value much less than full load cur rent Typical Motor Voltage Component Lead Mode Reading Main Winding Black to Start Line Voltage White Main Winding Black to Run Line Voltage White Start Winding Black to Start Line Voltage Red Start Winding Black to Run 120 Red Line Voltage 5 Motor voltage ch...

Page 7: ...7 THIS PAGE INTENTIONALLY LEFT BLANK ...

Page 8: ...o and from the factory or an authorized Pentair Hydromatic service facility This limited warranty will not apply a to defects or malfunctions resulting from failure to properly install operate or maintain the unit in accordance with the printed instructions provided b to failures resulting from abuse accident or negligence c to normal maintenance services and parts used in connection with such ser...