background image

Grounding the Plumbing

It is important that the plumbing system be electrically 

grounded. When a water softener is installed, a non-metallic 

bypass valve may interrupt the grounding. To maintain 

continuity, a grounding strap can be purchased at a hardware 

store (Figure 2). When installed, the strap will connect the 

inlet plumbing to the outlet plumbing to properly ground the 

system.
If you have other water treating equipment such as a 

chlorinator, sediment filter, neutralizer, iron filter, or taste 

and odor filter, they should be installed upstream of a water 

softener.
You may wish to consult a water professional if additional 

water treating equipment is to be installed.

Figure 2  

Bypass Valve

A bypass valve system should be installed on all water 

conditioning systems. Bypass valves isolate the conditioner 

from the water system and allow unconditioned water to be 

used. Service or routine maintenance procedures may also 

require that the system is bypassed. Figures 3 and 4 show the 

two common bypass methods.

Normal Operation

In Bypass

Water

Conditioner

In

Out

Water

Conditioner

In

Out

Figure 3  Series 1265 Bypass for Use  

with Performa Valve Bodies 

Water

Conditioner

Water

Conditioner

Normal Operation

In Bypass

Figure 4  Typical Globe Valve Bypass System

Brine Tank 

Normally one brine tank is needed for each media tank. The 

use of block salt or rock salt is not recommended. If a brine 

shelf is used, two brine tanks are required. This is due to 

the increased time needed to produce a concentrated brine 

solution when using a salt shelf. If rapid multiple exhaustions 

and regenerations are anticipated, do not use a salt shelf even 

if two brine tanks are used.

Drain Line Connection

NOTE:   

Standard commercial practices are expressed here. 

Local codes may require changes to the following 

suggestions. Check with local authorities before 

installing a water conditioning system.

• 

The unit should be above and not more than 20'  

(6.1 m) from the drain. Connect an appropriate adapter 

fitting and 3/4" (1.9 cm) plastic tubing to the drain line 

connection on the rear of the control valve.

• 

If the backwash flow rate exceeds 5 gpm (22.7 Lpm) or if 

the unit is located  20-40' (6.1-12.2 m) from drain, use 1" 

(2.5 cm) tubing. Use appropriate fittings to connect the 

tubing to the drain connection on valve.

• 

If the unit is located where the drain line must be 

elevated, the drain line may be elevated up to 5' (1.5 m), 

provided the run does 

not

 exceed 15' (4.6 m) and water 

pressure at the system is not less than 40 psi (2.76 

bar). Elevation can be increased by 2' (61 cm) for each 

additional 10 psi (.69 bar) of water pressure at the drain 

connector.

• 

When the drain line is elevated, but empties into a drain 

below the level of the control valve, form a 7" (18 cm) loop 

at the far end of the line so that the bottom of the loop is 

level with the drain line connection. This will provide an 

adequate siphon trap. When the drain empties into an 

overhead sewer line, a sink-type trap must be used.

Secure the end of the drain line to prevent it from moving (see 

Figure 5 Drain Line Connection):

1" AIR GAP

INCORRECT

Construct air gap as shown or purchase air

gap device as used with clothes washers.

CORRECT

Figure 5  Drain Line Connection

NOTE:   

Waste connections or the drain outlet should be 

designed and constructed to provide for connection to 

the sanitary waste system through an air gap of two 

pipe diameters or 1" (22 mm), whichever is larger. 

WARNING:

 Never insert a drain line directly into a drain, 

sewer line, or trap (Figure 5 Drain Line 

Connection). Always allow an air gap between 

the drain line and the wastewater to prevent 

the possibility of sewage being back-siphoned 

into the softener.

EQUIPMENT INSTALLATION 

CONTINUED

4

 

• 

AUTOTROL

®

 Logix 764 Control Performa Cv Series Valves (273, 278) Service Manual

Summary of Contents for AUTOTROL LOGIX 764

Page 1: ...AUTOTROL LOGIX 764 CONTROL PERFORMA CV SERIES VALVES 273 278 SERVICE MANUAL www pentairaqua com...

Page 2: ...grounding is maintained Mechanical Do not use petroleum based lubricants such as petroleum jelly oils or hydrocarbon based lubricants Use only 100 silicone lubricants All plastic connections should b...

Page 3: ...ity or water spray from below Examples are constant heavy mist near corrosive environment upwards spray from sprinkler CAUTION This unit is for dry location use only unless used with a Listed Class 2...

Page 4: ...e following suggestions Check with local authorities before installing a water conditioning system The unit should be above and not more than 20 6 1 m from the drain Connect an appropriate adapter fit...

Page 5: ...connection is tight Figure 8 Electrical Connection WARNING This valve and control are for dry location use only unless used with a Listed Class 2 power supply suitable for outdoor use The 764 Series...

Page 6: ...ut Main Motor Optical Sensor Connection Turbine Input No Salt Detector Chlorine Generator Connection Multi Single Tank Lockout Remote Regen Start Dry Contact Signal Input Connection Extension Cable Co...

Page 7: ...lve Discs One Piece Valve Disc Spring Optical Sensor Camshaft Motor Outlet Drain Inlet Backwash Drain Control Injector Screen Filter Control Module Mount 273 278 VALVE FEATURES Figure 13 273 278 Valve...

Page 8: ...nse cycle Water is directed to the regenerant tank at a controlled rate to create brine for the next regeneration SERVICE BACKWASH BRINE SLOW RINSE FAST RINSE From Regenerant Tank To Regenerant Tank B...

Page 9: ...s a standard 12 volt AC motor that works with either 50 Hz or 60 Hz The same motor is used worldwide and does not need to be changed for different power conditions Power 700 Series controllers are ava...

Page 10: ...ns the controller to normal operation Figure 17 NOTE In normal operation and during programming only a few of the icons will actually be displayed 1 This cursor is displayed when the days between rege...

Page 11: ...ontrol is powered up the display will show 255A 2 Use the or buttons to increment through the available selections Table 1 For the next steps you may want to remove the cover to watch the camshaft mov...

Page 12: ...e Salt Amount Time Day Regeneration Time Time Day Regeneration Time Buttons to Press Range 1 Resin Volume Select correct resin volume Cubic feet 0 25 to 3 00 2 Time of Day 12 hr Set to time of day Not...

Page 13: ...99 Minutes 0 to 200 Gallons 1 x 100 to 900 Control programmming is complete press or press press then or press press then or press press then or press press then or press press then or press press the...

Page 14: ...an be sent directly back to the treated water position from any regeneration cycle Press the UP and SET buttons for about five seconds until the hourglass icon begins flashing The control will now ski...

Page 15: ...Rinse C4 Standby Both tanks have now been purged of air The water supply valve can be fully opened 2 Press and hold the button for five seconds This will start the second regeneration Quick cycle as T...

Page 16: ...e controller is first plugged in it may display a flashing hourglass and the message Err 3 this means that the controller is rotating to the home position If the Err 2 is displayed check that the inco...

Page 17: ...o chlorine generator 1 Salt check only 2 Generate chlorine P14 Refill Rate 1 700 1 1 gpm x 100 P15 Draw Rate 1 700 1 1 gpm x 100 P16 Reserve Type not used for alternating mode 0 3 1 0 0 Variable reser...

Page 18: ...bs ft3 Under normal circumstances this setting will provide the correct system capacity This setting may be adjusted to change the exchange capacity see Table 4 Table 3 High Efficiency Exchange Capaci...

Page 19: ...ackwash 0 200 1 Min 10 Flow rate dictated by size of drain line flow controller C2 Regenerant Draw 0 200 1 Min See Notes Automatically calculated from resin volume and salt dosage settings C3 Slow Rin...

Page 20: ...Average usage for Monday in gallons or m3 0 131 070 gallons or 0 1 310 70 m3 H9 Average usage for Tuesday in gallons or m3 0 131 070 gallons or 0 1 310 70 m3 H10 Average usage for Wednesday in gallon...

Page 21: ...ate once Double Immediate Manual Regeneration Back to back manual regenerations are initiated by pressing and holding the REGEN button for three seconds while the control is in the regenerating mode A...

Page 22: ...ated sequentially the next time of regeneration regardless of how much water is used during that 24 hour period This feature is to help recover a severely exhausted bed See Table 8 P16 2 Immediate Reg...

Page 23: ...g back into one site To install control module Wire Clips Slots for Motor and Turbine Harness 1 Be sure the power is disconnected 2 Check model 3 Check routing of wires and plug them into the controll...

Page 24: ...haft numbers are visible in the hollow of the cup An arrow on the top plate points to the current marking The numbers represent regeneration cycles as follows C0 Treated water normal operation mode C1...

Page 25: ...top plate This switch is turned on off by a cam lobe on the camshaft Its function is to signal that the unit is in service or out of service regenerating Microswitches are available as kits from Pent...

Page 26: ...t to repair a bent spring 2 Position yourself on the spring side of the valve discs 3 Position the spring over the valve body close to final position The wide spring segments will be located at the wi...

Page 27: ...dure to engage the screws with the existing threads If the same threads are not used the holding power of the screw is lost Under pressure the valve can leak Screws that have the same diameter but hav...

Page 28: ...ose sold for commercial laundries adjust the dosage accordingly 1 Dosage Polystyrene resin 1 2 fluid ounce 35 5 mL per cubic foot Non resinous exchangers 0 8 fluid ounce 23 7 mL per cubic foot 2 Regen...

Page 29: ...between tank 1 and tank 2 controls Figure 21 outlines these standard features P4 BL BRN WHT YEL ORG P2 Flow Sensor Optical Sensor Motor 80 in 2017 mm P3 2 BLK GRN R Logix 764 control on Tank 1 R GRN...

Page 30: ...gix 764 control on Tank 1 Logix 764 control on Tank 2 BLK GRN RED BLK GRN RED BLK GRN RED BLK GRN Repeat for all remaining tanks Logix 764 control on Tank 3 Figure 23 NOTE Cable PN 3020228 sold separa...

Page 31: ...ASSEMBLY DIAGRAMS 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 12 20 21 22 23 24 25 273 278 Exploded View Parts List AUTOTROL Logix 764 Control Performa Cv Series Valves 273 278 Service Manual 31...

Page 32: ...Lt Purple 9 inch tank 1035734 J Injector Lt Blue 10 inch tank 1035735 K Injector Pink 12 inch tank 1035737 M Injector Brown 14 inch tank 1035738 N Injector Green 16 inch tank 1035739 Q Injector Purpl...

Page 33: ...ASSEMBLY DIAGRAMS CONTINUED BYPASS BYPASS 1 1 1040930 1265 Bypass Item No QTY Part No Description 1 Bypass Valve AUTOTROL Logix 764 Control Performa Cv Series Valves 273 278 Service Manual 33...

Page 34: ...long PVC 255 Ry 4 Pipe Tube Adapter Nut 1 42 ID Universal 2 1265 Bypass w Install Kit No Adapters Single Pack 3019932 74 Manifold Kit 1 in PVC w No Bypass 2 Pipe Fitting Tee 1 in 2 Pipe Fitting Elbow...

Page 35: ...in the Logix controller ERR 4 is displayed If single tank system Verify system setting is programmed to 273 278 L Controller on tank 2 does not know the position of the camshaft Camshaft should be ro...

Page 36: ...power Defective motor Replace motor Contact dealer Control regenerates at wrong time of day Controller set incorrectly Correct time setting according to instructions Valve will not draw regenerant Low...

Page 37: ...ill Flush out foreign matter holding disc open by manually operating valve stem Air leak in regenerant line to air check Check all connections in regenerant line for leaks Refer to instructions Improp...

Page 38: ...Valve No 1 Open 2 Open 3 Closed 4 Closed 5 Closed 6 Open 7 Closed Backwash Position Brine Tank Mineral Tank Drain Inlet Outlet Hard Water Soft Water 5 4 1 3 2 6 7 Backwash Flow Control Valve No 1 Clos...

Page 39: ...ed 2 Open 3 Open 4 Closed 5 Closed 6 Open 7 Closed Refill Position Brine Tank Mineral Tank Drain Inlet Outlet Hard Water Soft Water 5 4 1 3 2 6 7 Valve No 1 Closed 2 Closed 3 Open 4 Open 5 Open 6 Clos...

Page 40: ...LWR6151 20 2 3 5 5 6 7 5 40 60 80 100 120 Injector J Light Blue For 10 inch Tanks TOTAL BRINE DRAW RINSE Gallons per Minute bar PSI 0 25 0 20 0 15 0 10 0 05 0 00 3 m hr 1 20 1 00 0 80 0 60 0 40 0 20...

Page 41: ...Flow Data 0 80 0 70 0 60 0 50 0 40 0 30 0 20 0 10 0 00 3 50 3 00 2 50 2 00 1 50 1 00 0 50 0 00 Gallons per Minute bar PSI m3 hr 20 40 60 80 100 120 Injector R Dark Grey For 21 inch Tanks TOTAL BRINE...

Page 42: ......

Page 43: ......

Page 44: ...s and logos are the property of their respective owners Because we are continuously improving our products and services Pentair reserves the right to change specifications without prior notice Pentair...

Reviews: