LEVEL III CYCLE PROGRAMMING
C Values
Several Level III program parameters can be adjusted to fine-
tune valve operation for non-standard applications. Typically
these parameters will not need to be adjusted as the default
settings accommodate most applications. Contact your water
treatment professional before attempting any programming.
The parameters are accessible by pressing and holding the UP
and SET buttons until the display shows a “C” value.
NOTE:
The control must be in the treated water position to
change settings.
Table 4 Level III Parameters
C#
Description
Range
Minimum
Increments
Default
Setting
Notes
C1
Backwash
0-200
1 Min
10
Flow rate dictated by size of drain line flow
controller.
C2
Regenerant Draw
0-200*
1 Min
See Notes
Automatically calculated from resin volume and
salt dosage settings.
C3
Slow Rinse
0-200
1 Min
See Notes
Automatically calculated from resin volume and
salt dosage settings.
C4
Re-pressurization
0-200
1 Min
3
Allows system to equalize water pressure across
valve discs.
C5
Fast Rinse
0-200
1 Min
4
Rinses residual regenerant from tank.
C8
Regenerant Refill
0-200*
1 Min
See Notes
Automatically calculated from resin volume and
salt dosage settings.
* C2 and C8 are automatically calculated and not adjustable when 268 softener is selected. C2 and C8 are adjustable when 273 filter is selected
but are not used by the system.
AUTOTROL
®
Logix 764 Control Performa Cv Series Valves (273, 278) Service Manual
•
19