TYPICAL INSTALLATION OF 1080-ST HEAT 

EXCHANGER SHOWING RECOMMENDED METHOD 

OF INSTALLING CONVERTERS WITH AURORA AIR 

CONTROL SYSTEM:

To establish air control in converter or heat exchanger 

installations, a pipe mounted air eliminator is installed as 

shown in the accompanying diagram. The vortex air separator 

consists of a large cross-sectional area reducing the flow 

velocity and allowing air bubbles to rise into the air line to the        

compression tank.

1.  The air line from the vortex air separator must pitch up to 

the air control tank fitting and compression tank.

2.  The pump must be installed in the supply main, pumping to 

the system, regardless of the size of converter or pump. In 

this way, pump head is added to the piping circuit.

Steam hammer can cause serious damage to the tubes 

of any heat exchanger. A careful consideration of the 

following points before an installation is made can 

prevent costly repairs which may be caused by a steam 

hammer.

1.  A vacuum breaker and/or vent should be used in accordance 

with the type of alarm system installed.

2.  The proper trap should be used for the steam system 

installed.

3.  The trap and one condensate return line to the trap should be 

properly sized for the total capacity of the converter.

4.  The trap should be sized for the pressure at the trap, not the 

inlet pressure to the steam controller.

CAUTION

STEAM 

TRAP

CONVERTER

RELIEF

VALVE

PRESSURE

REDUCING

VALVE

PIPE-

MOUNTED

AIR

ELIMINATOR

STEAM CONTROL VALVE

AIR CONTROL

TANK FITTING

AIR CUSHION TANK

FLO-CONTROL

VALVE

CIRCULATOR