background image

© 2013 Pentair Equipment Protection

87976540

- 6 -

TEMPERATURE CONTROL

The electromechanical thermostat is factory preset to 75 F/23 C. To change the temperature setting, remove the 

front cover. Use a standard screwdriver to adjust thermostat. For cooler temperatures turn clockwise, for warmer 

temperatures turn counterclockwise.

WATER USAGE

CONDENSER

The water cooled air conditioner uses water as the cooling medium for the condensing side of the hermetic 

refrigeration system. This water is passed through a heat exchanger that uses the cool water to lower the 

temperature of the hot gaseous refrigerant, causing it to condense.  The water is warmed by this exchange of 

heat, and is passed out of the air conditioner at an elevated temperature.  The inlet and outlet water fittings are 

located on the bottom of the air conditioner. A sealant is recommended when connecting the inlet and outlet 

water lines to prevent leakage. It is extremely important for the air conditioner to have an uninterrupted supply of 

clean cooling water.  Interference with the water supply will cause the unit to automatically shut down and require 

manual reset.

MANUAL RESET HIGH PRESSURE LIMIT SWITCH

The manual reset high pressure limit switch is located behind the front cover.  This limit switch interrupts 

compressor operation when condenser refrigerant exceeds 310 PSIG, which most frequently occurs as a result 

of the condenser water supply being reduced or shut down.  After identifying and correcting the problem with the 

water supply to the unit, compressor operation can be restored by pushing the manual reset button located on the 

switch.

WATER VALVE

The valve that controls the flow of condensing water is also located behind the front cover. This valve modulates 

the flow of water to the condensing coil.  Water flow varies according to a variety of loading conditions, including 

electrical load, inlet water temperature, ambient air temperature, cabinet construction, etc.  The maximum 

flow rate in the Design Data on page 4 is given for the conditions of maximum rated load, maximum water 

temperature, and maximum ambient temperature, and reflects the highest flow rate anticipated for the unit. 

NOTE: This valve has been preset at the factory for the correct operation of the unit. The setting of the valve 

should not be altered.

WATER

The air conditioner water supply does not require special treatment, but care should be taken to avoid any gross 

contamination.  Corrosives may cause leakage within the coil and water lines.  Mineral rich water will cause 

scaling of the coil, degrading performance.  Particulates may cause rapid erosion of the coil, and could result in 

clogging of the control valve. NOTE: A filter to clean the air conditioner water supply is recommended.
If the temperature of the inlet water is higher than that shown in the Design Data on page 4, it will result in a 

higher flow rate, and may cause shut-down of the unit. High inlet water temperatures should be avoided.
When the air conditioner is shut-down, either because of a thermostatic cut-out or a loss of power, the water 

flow should gradually diminish to zero.  If water flow persists, it may indicate a malfunction of the control valve.  

Information on the specific valve employed is supplied with the air conditioner.

Summary of Contents for 33WC

Page 1: ... 2013 Pentair Equipment Protection 87976540 Rev L P N 10 1008 63 Water Cooled Indoor Air Conditioner 33WC Model INSTRUCTION MANUAL ...

Page 2: ...rmation is required TABLE OF CONTENTS HANDLING TESTING THE AIR CONDITIONER 3 INSTALLATION INSTRUCTIONS 4 TECHNICAL INFORMATION 4 Design Data 4 DIMENSIONAL DRAWING 4 PRINCIPLES OF OPERATION 5 Mounting Gasket 5 TEMPERATURE CONTROL 6 WATER USAGE 6 Condenser 6 Manual Reset High Pressure Limit Switch 6 Water Valve 6 Water 6 MAINTENANCE 7 Compressor 7 Evaporator Blower 7 Refrigerant Loss 7 Freezing and ...

Page 3: ...ioner and also voids the warranty CAUTION Refer to the nameplate for proper electrical current requirements then connect power cord to a properly grounded power supply Minimum circuit ampacity should be at least 125 of the amperage shown in the design data section for the appropriate model No other equipment should be connected to this circuit to prevent overloading Connect to clean pressurized wa...

Page 4: ... clean pressurized water supply Allow unit to remain upright for a minimum of five 5 minutes before starting Caution Air conditioner must be in upright position during operation 5 Refer to top of nameplate for electrical requirements Connect the power cord to a properly grounded power supply Use of an extension cord is not recommended Electrical circuit should be fused with slow blow or HACR circu...

Page 5: ...der for the air conditioner to restart Operating the air conditioner below the minimum ambient temperature or above the maximum ambient temperatures indicated on the nameplate voids all warranties It is recommended that the warranty section of this manual be read in order to familiarize yourself with parameters of restricted operation The moisture that the enclosure air can contain is limited If m...

Page 6: ...essor operation can be restored by pushing the manual reset button located on the switch WATER VALVE The valve that controls the flow of condensing water is also located behind the front cover This valve modulates the flow of water to the condensing coil Water flow varies according to a variety of loading conditions including electrical load inlet water temperature ambient air temperature cabinet ...

Page 7: ...ic leaks not found with sensitive electronic refrigerant leak detection equipment during manufacture may require repair or recharging of the system This work should only be performed by qualified professionals generally available through a local reputable air conditioning repair or service company Refer to the data on the nameplate which specifies the type of refrigerant and the charge size in oun...

Page 8: ... 00 52 6028 00 52 6028 00 52 6028 00 Mounting Gasket Kit 33 1000 00 33 1000 00 33 1000 00 33 1000 00 Evaporator Fan 12 1012 101 12 1012 102 12 1012 101 12 1012 102 Compressor 10 1016 23 10 1026 74 10 1016 22 10 1026 74 Thermal Overload 10 1007 19 10 1007 57 10 1007 44 10 1007 57 Compressor Relay 10 1028 20 10 1028 07 10 1028 05 10 1028 07 Start Capacitor None 10 1032 09 None 10 1032 09 For additio...

Page 9: ... 2013 Pentair Equipment Protection 87976540 9 NOTES ...

Page 10: ...otective coatings and or options and is in an abnormal or corrosive environment voids the warranty Prolonged operation with dirty filters also voids the warranty Should any part prove defective within the above warranty period the customer may choose to return the defective product that is under warranty to Pentair Equipment Protection for repair at no charge or the customer has the option to repa...

Page 11: ...tair Equipment Protection in writing of any such claim or demand provided further that Pentair Equipment Protection shall have the right and option to undertake and control the entire defense of such claim or demand instituted against the customer or user but limited to the products made or sold by Pentair Equipment Protection through counsel selected by Pentair Equipment Protection and to settle ...

Page 12: ... 2013 Pentair Equipment Protection 87976540 Rev L P N 10 1008 63 Pentair Equipment Protection 2100 Hoffman Way Minneapolis MN 55303 USA 1 763 422 2211 1 763 576 3200 PentairEquipmentProtection com ...

Reviews: