background image

© 2013 Pentair Equipment Protection

87976540

- 3 -

RECEIVING THE AIR CONDITIONER

Inspect the air conditioner. Check for concealed damage that may have occurred during shipment. Look for 

dents, scratches, loose assemblies, etc. Damage evident upon receipt should be noted on the freight bill. Damage 

should be brought to the attention of the delivering carrier -- NOT to Pentair Equipment Protection -- within 

15 days of delivery. Save the carton and packing material and request an inspection. Then file a claim with the 

delivering carrier.
Pentair Equipment Protection cannot accept responsibility for freight damages; however, we will assist you in any 

way possible.

HANDLING & TESTING THE AIR CONDITIONER

TEST FOR FUNCTIONALITY BEFORE MOUNTING THE AIR CONDITIONER TO THE ENCLOSURE.
If it is necessary to place the air conditioner in a horizontal position after unpacking, be certain it is placed in an 

upright, vertical or mounting position for a minimum of five (5) minutes before operating.

Do not attempt to operate the air conditioner while it is horizontal 

or on its side, back or front. The refrigeration compressor is filled 

with lubricating oil. This will cause permanent damage to the air 

conditioner and also voids the warranty.

CAUTION

Refer to the nameplate for proper electrical current requirements, then connect power cord to a properly 

grounded power supply. Minimum circuit ampacity should be at least 125% of the amperage shown in the design 

data section for the appropriate model. No other equipment should be connected to this circuit to prevent 

overloading.
Connect to clean, pressurized water supply and provide drain.
Operate the air conditioner for five (5) to ten (10) minutes. No excessive noise or vibration should be evident 

during this run period. The evaporator blower (enclosure air), and the compressor should be running.
The compressor is provided with automatic reset thermal overload protection. This thermo-switch is located and 

mounted inside the plastic enclosure clipped to the compressor. The only time this switch should operate is when 

the compressor overheats due to ambient air temperatures exceeding nameplate rating or if enclosure dissipated 

heat loads exceed the rated capacity of the air conditioner. The thermal overload switch will actuate and stop 

compressor operation. The blower will continue to operate and water will continue to flow for a short period. The 

compressor will restart after it has cooled to within the thermal overload cut-in temperature setting.
The unit will also shut down if water supply is interrupted. See WATER USAGE on page 6.

Summary of Contents for 33WC

Page 1: ... 2013 Pentair Equipment Protection 87976540 Rev L P N 10 1008 63 Water Cooled Indoor Air Conditioner 33WC Model INSTRUCTION MANUAL ...

Page 2: ...rmation is required TABLE OF CONTENTS HANDLING TESTING THE AIR CONDITIONER 3 INSTALLATION INSTRUCTIONS 4 TECHNICAL INFORMATION 4 Design Data 4 DIMENSIONAL DRAWING 4 PRINCIPLES OF OPERATION 5 Mounting Gasket 5 TEMPERATURE CONTROL 6 WATER USAGE 6 Condenser 6 Manual Reset High Pressure Limit Switch 6 Water Valve 6 Water 6 MAINTENANCE 7 Compressor 7 Evaporator Blower 7 Refrigerant Loss 7 Freezing and ...

Page 3: ...ioner and also voids the warranty CAUTION Refer to the nameplate for proper electrical current requirements then connect power cord to a properly grounded power supply Minimum circuit ampacity should be at least 125 of the amperage shown in the design data section for the appropriate model No other equipment should be connected to this circuit to prevent overloading Connect to clean pressurized wa...

Page 4: ... clean pressurized water supply Allow unit to remain upright for a minimum of five 5 minutes before starting Caution Air conditioner must be in upright position during operation 5 Refer to top of nameplate for electrical requirements Connect the power cord to a properly grounded power supply Use of an extension cord is not recommended Electrical circuit should be fused with slow blow or HACR circu...

Page 5: ...der for the air conditioner to restart Operating the air conditioner below the minimum ambient temperature or above the maximum ambient temperatures indicated on the nameplate voids all warranties It is recommended that the warranty section of this manual be read in order to familiarize yourself with parameters of restricted operation The moisture that the enclosure air can contain is limited If m...

Page 6: ...essor operation can be restored by pushing the manual reset button located on the switch WATER VALVE The valve that controls the flow of condensing water is also located behind the front cover This valve modulates the flow of water to the condensing coil Water flow varies according to a variety of loading conditions including electrical load inlet water temperature ambient air temperature cabinet ...

Page 7: ...ic leaks not found with sensitive electronic refrigerant leak detection equipment during manufacture may require repair or recharging of the system This work should only be performed by qualified professionals generally available through a local reputable air conditioning repair or service company Refer to the data on the nameplate which specifies the type of refrigerant and the charge size in oun...

Page 8: ... 00 52 6028 00 52 6028 00 52 6028 00 Mounting Gasket Kit 33 1000 00 33 1000 00 33 1000 00 33 1000 00 Evaporator Fan 12 1012 101 12 1012 102 12 1012 101 12 1012 102 Compressor 10 1016 23 10 1026 74 10 1016 22 10 1026 74 Thermal Overload 10 1007 19 10 1007 57 10 1007 44 10 1007 57 Compressor Relay 10 1028 20 10 1028 07 10 1028 05 10 1028 07 Start Capacitor None 10 1032 09 None 10 1032 09 For additio...

Page 9: ... 2013 Pentair Equipment Protection 87976540 9 NOTES ...

Page 10: ...otective coatings and or options and is in an abnormal or corrosive environment voids the warranty Prolonged operation with dirty filters also voids the warranty Should any part prove defective within the above warranty period the customer may choose to return the defective product that is under warranty to Pentair Equipment Protection for repair at no charge or the customer has the option to repa...

Page 11: ...tair Equipment Protection in writing of any such claim or demand provided further that Pentair Equipment Protection shall have the right and option to undertake and control the entire defense of such claim or demand instituted against the customer or user but limited to the products made or sold by Pentair Equipment Protection through counsel selected by Pentair Equipment Protection and to settle ...

Page 12: ... 2013 Pentair Equipment Protection 87976540 Rev L P N 10 1008 63 Pentair Equipment Protection 2100 Hoffman Way Minneapolis MN 55303 USA 1 763 422 2211 1 763 576 3200 PentairEquipmentProtection com ...

Reviews: