MAINTENANCE INSTRUCTIONS
44
P
ARAMETER
21
–
I
GNITION
S
EQUENCE
S
ETTING
I
GNITION POINT IN
H
Z
6. Use buttons ‘+’ o ‘-’ to modify the value of the parameter
between: min = value of parameter 17; max = value of
parameter 18.
The default value is:
- 90Hz for Natural Gas;
- 110 Hz for L.P.G.;
7
.
Press and release button ‘S’ to confirm. The parameter
number (21) will appear in the display.
8. Switch off the appliance and switch it back on again to
render the new parameter operative.
P
ARAMETER
22
–
F
AN
F
REQUENCY VALUE DISPLAY
6. Use buttons ‘+’ o ‘-’ to modify the value of the parameter:
- 00 = Off
- 01 = On
If parameter value 01 is selected, during the boiler operation,
the display will show the fan frequency value for 10 min.
7. Press and release button ‘S’ to confirm. The parameter
number (22) will appear in the display.
8. Switch off the appliance and switch it back on again to
render the new parameter operative.
P 21
S
S
S
S
110
00
P 22
110V 60Hz
110V 60Hz
110V 60Hz
110V 60Hz