18
Set Battery Alarm Trigger Voltage
Command:
Change battery alarm to XX.X
Where XX.X can be between 8 and 30 volts
The system responds with:
The low voltage alarm has been set to XX.X
volts and the alarm has been reset
This system monitors the battery by calculating the average value of the supplied voltage over
the previous 1 minute period. Once this average has been detected to be below the set value
for the programmed time it sends a text message to inform all users. The inclusion of the
running average helps protect the system from detecting inaccurate readings during periods
of increased load.
If no value (XX.X) is set the system responds with:
Because no value was specified the voltage alarm has been set to 11.5 volts and the
alarm has been reset
If the value (XX.X) is outside the settings the system responds with:
Because the value is out of range the voltage alarm has been set to 11.5 volts and
the alarm has been reset
Link the Battery Alarm to an Output
Command:
Link battery alarm to
OUTPUT NAME
The system responds with:
The battery alarm has successfully been linked to
OUTPUT NAME and the alarm has
been reset
To clear or remove the link
Command:
Clear battery link
The system responds with:
The battery alarm Output link has been removed
Function:
If a link is setup between the Battery Alarm and an Output, then when the Battery
Alarm turns ON, the linked Output will also turn on. Full control of the Output is still available
(see page 15-16).
Check the Battery Supply Voltage
Command:
Voltage status
The system responds with: (where battery is the name for the supply voltage)
Battery is currently XX.X volts
Ezy Switch SMS-TEMP-4 Installation & Operation