HUM2ESXX CONFIGURATION 

 

 
 
 
 
 
 

1

ST

 LEVEL VALUES 

 
1. 1

st

 level default values are the same for all humidifier models. 

 

2.  To access the first level programming menu follow the instructions below: 

- Simultaneously keep keys UP (

5

) and DOWN (

6

) pressed until the first programming 

variable appears on the display.  
- Release keys (

5

) and (

6

- Select the variable to amend using key (

5

) or key (

6

). 

- After having selected the wanted variable it will be possible: 
- To display its setting by pressing the SET key 
- To amend the setting by keeping the SET key pressed and by pressing one of the (

5

) or (

6

keys. To exit the menu once the configuration values are set, simultaneously keep keys (

5

) and 

(

6

) pressed for a few seconds until the size displayed before entry to programming appears 

again, e.g. steam output or absorbed current. Memorisation of the amendments made to the 
variables will happen automatically when exiting the configuration menu. 

 

VAR. 

MEANING 

VALUES 

DEFAULT 

all models 

Pr 

Steam output percentage 

20 ÷ 100 % 

100 % 

Bp 

Proportional band  

1 ÷ 20 Rh% 

10 % 

StC 

Max humidity set point in channel.  

25 ÷ 99 Rh% 

99% 

r0 

Max humidity set differential in channel. 

1 ÷ (StC – 20) Rh% 

50% 

r1 

Temperature differential referred to set point. 

0.2 – 10°C 

2°C 

UrC 

Humidity value read by the channel probe 

0-100% 

read only 

 
 
 
 

2

ND

 LEVEL VALUES 

 
1. Set the 2

nd

 level default values referring to the humidifier model upon which the kit will be 

mounted, following the summarised table carried hereafter (the values shown are the only values 
to be modified since they are different from one size to another): 
 

2. To access second level programming, keep the UP (

5

), DOWN (

6

) and WATER 

DISCHARGE keys pressed for a few seconds.  When the first programming variable appears, 
the system automatically switches to stand-by. 
- Select the variable to amend using key (

5

) or key (

6

). 

- After having selected the wanted variable it will be possible: 
- To display its setting by pressing the SET key 
- To amend the setting by keeping the SET key pressed and by pressing one of the (

5

) or (

6

keys. 

CHAP. 3 SETTING DEFAULT VALUES 

3.2

3.1

Summary of Contents for EasySteam 400HUM2ESXX

Page 1: ...ELECTRONIC KIT 400HUM2ESXX 400KHUM2ESXX INSTALLATION MANUAL REV 01 11 EN...

Page 2: ...RODUCTION Page 2 1 1 Generality CONFIGURATION Page 3 2 1 Hardware configuration Page 4 2 2 Software configuration SETTING DEFAULT VALUES Page 5 3 1 1st level values Page 5 3 2 2nd level values TABLE O...

Page 3: ...uire the presence of the display and can be used independently It is also provided with status LED and switch jumper for the manual discharging of the cylinder The 400KHUM2ESXX electronic kit is suppl...

Page 4: ...ing to 1 fig 1 Jumper J2 has 2 possible positions the jumper can be connected in position 1 2 or position 2 3 Table 1 hardware setting correspondence through jumper J2 and humidifier size ES series hu...

Page 5: ...e Keeping the SET button pressed increases or decreases the value I1 by using the UP or DOWN keys Release the SET button The set value is now memorised by the software To exit programming press the UP...

Page 6: ...AR MEANING VALUES DEFAULT all models Pr Steam output percentage 20 100 100 Bp Proportional band 1 20 Rh 10 StC Max humidity set point in channel 25 99 Rh 99 r0 Max humidity set differential in channel...

Page 7: ...pump activation 1 50 25 25 20 15 S7 Pump discharge duration time for overcurrent 0 1 5 0 s 0 5 0 5 0 5 0 5 S8 Minimum current differential for water charge 0 0 5 0 A 0 1 0 1 0 3 0 5 S9 Functioning se...

Page 8: ...a Piacentina 6 b 45030 Occhiobello ROVIGO ITALY Tel 39 0425 762906 Fax 39 0425 762905 e mail info pego it www pego it Dealer Document code 400 HUM2ESXX ELECTRONIC KIT rel 01 11 ITA PEGO s r l reserves...

Reviews: