INSTALLING THE IN-ROOM EMERGENCY PUSHBUTTON

 

1.

The in-room pushbutton must be positioned so that it is always visible and easily

reachable.

2.

Undo the two closure screws on the front of the pushbutton panel.

3.

Using the two internal holes fix the box backing with three screws of a length suitable for

the thickness of the wall to which it is to be attached.

OPERATION AND MAINTENANCE

 

-

Carry out the connections as per the wiring diagram.

-

After initial connection it will take 110 hours to fully charge the battery.

-

Press the luminous pushbutton installed inside the cold room to activate the

 

acoustic

and luminous warning devices on the external alarm control unit.
The auxiliary relay contact closes.

-

- To deactivate the alarm, pull out the emergency illuminated push button again

(unlock)

-

In the event of a 230 V AC power failure the buffer battery will intervene and power
the system for the duration indicated on the technical characteristics chart.

-

Reset the emergency switch inside the cold room to cancel the alarm.

-

Periodically check that the buffer battery is working properly.

-

If the battery is replaced make sure it is disposed of properly at an authorised waste
collection facility.

-

If the alarm is tripped without the pushbutton being pressed check the connection
lead and the connections between the pushbutton and external control unit.

SPARE PARTS: 

Buffer battery: ACC12VNIMH 

2.2

2.3

CHAP. 2 - Installation

- ENG -

USE AND MAINTENANCE MANUAL

 

Summary of Contents for 6CIAPE03

Page 1: ...Alle Angaben sind ohne Gew hr nderungen bleiben CI GmbH CONTROL INSTRUMENTS vorbehalten V 2201 001 manual ECP APE 03...

Page 2: ...HBUTTON UNIT Page 3 1 6 IDENTIFICATION DATA Page 4 1 7 DESCRIPTION OF SYSTEM INSTALLATION Page 5 2 1 INSTALLING THE OUT OF ROOM ALARM CONTROL UNIT Page 6 2 2 INSTALLING THE IN ROOM EMERGENCY PUSHBUTTO...

Page 3: ...n mains power 20 mA Buffer battery 12 V DC Ni MH 1300 mAh Complete recharge time 110 h Operating autonomy With 230 V AC NOT ON running on charged buffer battery 14 h approx With 230 V AC power ON unli...

Page 4: ...IFICATION DATA The unit described in this manual has on its side an ID plate showing all the relevant identification data Name of Manufacturer Code and model of UNIT electrical board Serial number IP...

Page 5: ...mushroom type button with N C contact The pushbutton is permanently lit by LEDs so that it can be located in the dark Acoustic visual alarm control unit to be fitted outside the cold room Features a s...

Page 6: ...ng model see relative table in APPENDICES To effect correct electrical connection and maintain the protection rating use appropriate wire raceway grips to ensure a good seal Route the wiring inside th...

Page 7: ...nous warning devices on the external alarm control unit The auxiliary relay contact closes To deactivate the alarm pull out the emergency illuminated push button again unlock In the event of a 230 V A...

Page 8: ...TTACHMENT SCREWS 4 BUFFER BATTERY SUPPORT FIXING SCREWS 5 BOARD 6 BUFFER BATTERY SUPPORT METAL SHEETING 9 FRONTAL SECTION IN ABS 10 ACOUSTIC VISUAL ALARM 11 BOX CLOSURE SCREWS 12 ACOUSTIC VISUAL ALARM...

Page 9: ...ions have been made it is therefore necessary to connect this fastom to the connector marked 1 on the upper left side of the board as also indicated on the wiring diagram It is advisable to first conn...

Page 10: ...r internal components or any work carried out in a way that fails to comply with the information instructions in this manual shall render the warranty null and void immediately Modifications improper...

Page 11: ...I DELLE SEGUENTI NORME comprese tutte le modifiche THE CONFORMITY WITH THE REQUIREMENTS OF THIS DIRECTIVE IS TESTIFIED BY COMPLETE ADHERENCE TO THE FOLLOWING STANDARDS including all amendments Norme a...

Page 12: ...CI GmbH CONTROL INSTRUMENTS Baumschulenweg 10 70736 Fellbach DE www ci gmbh com info ci gmbh com 49 711 65883 0...

Reviews: