- 66 -
7 Inspection
1
5
2
6
3
7
9
4
8
10
Inspection of leakage and wiring condition
1
Check if there is no leakage of cooling water, sub-engine oil or sub-engine
fuel from the tanks, pipes or connecting parts.
2
Check if there is no damage on the wire connected to the battery.
3
If any abnormal conditions are detected, contact your nearest dealer.
Inspection with the sight glass
1
Run the refrigeration unit for 10 minutes.
2
Check if the check color appears in green.
ADVICE
●
If the check color appears in yellow, contact your nearest dealer.
When operating the refrigeration unit with low inside container
temperature continuously for a long period
When operating the refrigeration unit continuously for a long period at 10°C or
lower, ice adheres to the drain pan and so on. Stop the unit operation once or
twice a week, and keep the door open to return the inside temperature to normal
so that the ice in the drain pan is melted.
Check color