48
TROUBLESHOOTING
Table 10.2 (cont.): Blocking Errors
Error No.
Error Display
Corrective Action
125
OUTDOOR_OPEN
Outdoor Sensor open
– Check sensor wiring for solid connection and continuity. Replace wiring if bad
or repair break.
– Check for resistance though the sensor by touching meter leads across both
pins on the sensor. If no circuit is present replace sensor.
126
RETURN_SHORTED
Return Sensor Shorted
– Check for resistance through the sensor by touching meter lead across both pins
on the sensor. Resistance should be between 15 k
Ω
and 500
Ω
. If no resistance is
present replace sensor.
127
SUPPLY_SHORTED
Supply Sensor 1 Shorted
– Check for resistance though the sensor by touching meter leads across the left
two pins on the sensor using when the retaining clip is towards you. . Resistance
should be between 15 k
Ω
and 500
Ω
. If no resistance is present replace sensor.
128
SUPPLY2_SHORTED
Supply Sensor 2 Shorted
– Check for resistance though the sensor by touching meter leads across the
left two pins on the sensor using when the retaining clip is towards you.
Resistance should be between 15 k
Ω
and 500
Ω
. If no resistance is present
replace sensor.
129
DHW_SORTED
DHW Sensor Shorted
– Check for resistance through the sensor by touching meter lead across both
pins on the sensor. Resistance should be between 15 k
Ω
and 500
Ω
. If no
resistance is present replace sensor.
130
FLUE_SHORTED
Flue Sensor Shorted
– Check for resistance through the sensor by touching meter lead across both
pins on the sensor. Resistance should be between 15 k
Ω
and 500
Ω
. If no
resistance is present replace sensor.
132
OUTDOOR_SHORTED
Outdoor Sensor Shorted
– Check for resistance through the sensor by touching meter lead across both
pins on the sensor. Resistance should be between 15 k
Ω
and 500
Ω
. If no
resistance is present replace sensor.
133
NET_FREQ_ERROR
Net freq. error detected by the watchdog. If error persists, replace control.
134
RESET_BUTTON_ERROR
TToo many resets in a short time period
– Allow a 1 hour wait period for error to clear.
– Cycle power
135
PHASE_NEUTRAL_RESERVED_ERROR
The line and neutral of the main voltage power supply input are reversed.
– Check line in power polarity. Correct if reversed.
155
WD_CONFIG_ERROR
Watchdog fan configuration setting error. If error persists, replace control.
156
FLUE_PRESSURE_ERROR
Blocked Flue/ Condensate Switch closed.
– Check for blockages in the vent pipe or heat exchanger.
– Check for blockages in the condensate system inside or after the
condensate trap. A slow drainage of condensate could cause condensate
back up that will trip this switch under certain conditions.
162
FILL_WARNING
Pressure is too low, demand has stopped, but no error needs to be stored at
this time
165
VSUPPLY_TOO_LOW
Main supply voltage too low for more than 60 seconds
– Check supply voltage for values below 108 Volts
166
VSUPPLY_TOO_HIGH
Main supply voltage too high for more than 60 seconds
– Check supply voltage or values above 132 Volts.
Summary of Contents for PBC-34
Page 22: ...20 WATER PIPING AND CONTROLS Figure 4 6 Recommended Central Heat Piping...
Page 23: ...21 Figure 4 7 Recommended Domestic Hot Water Piping WATER PIPING AND CONTROLS...
Page 31: ...29 Figure 7 2 Wiring Schematic and Connection ELECTRICAL CONNECTIONS...
Page 45: ...E LIGHTING OPERATING PROCEDURES 43 START UP PROCEDURE...
Page 57: ...THIS PAGE INTENTIONALLY LEFT BLANK...
Page 60: ...58 REPAIR PARTS Figure 13 2 PBC 34 Combustion Components...
Page 62: ...60 REPAIR PARTS Figure 13 3 PBC 40 and PBC 52 Combustion Components...