42
a. Using a combustion analyzer with the capability to
read carbon dioxide (CO2) and carbon monoxide
(CO), place the probe into the combustion test
port. See Figure 9.2.
b. Manually set the boiler to Maximum power by
entering the System Test Mode.
• Verify that the fan speed indicated is within 50
rpm of the maximum power fan speed in
Table 12.3. Status Menu parameter 1040.
• Verify that the CO and CO2 emissions are
within the parameters specified in Table 5.4.
c. Manually set the boiler to Low Power by entering
the System Test Mode.
• Verify that the fan speed indicated is within
100 rpm of the Low Power fan speed listed in
Table 12.3. Status Menu parameter 1040.
• Verify that the CO and CO
2
emissions are
within the parameters specified in Table 5.4.
d. If the values in either of these instances falls outside
the parameters listed in Table 5.4, turn off the
boiler and contact your PB Heat representative. For
best results, the value should be set for the middle
of the range (9% for Natural Gas and 10% for
LP Gas).
e. Be sure to set the System Test mode to Off so that
the boiler will modulate correctly in accordance
with the load.
f.
After removing the analysis probe from the vent
pipe, securely screw the analysis port cap back
onto the vent adapter.
g. Record the combustion readings on the “Start-up
Combustion Record” in Appendix D. It is very
important to record all of the information
requested on the sheet for follow up and
troubleshooting.
START-UP PROCEDURE
To prevent moisture damage to control and blower:
During Boiler operation verify that there are no water leaks from any fittings on the boiler header and that
all vent connections are water tight and properly assembled.
NOTICE
Summary of Contents for PBC-34
Page 22: ...20 WATER PIPING AND CONTROLS Figure 4 6 Recommended Central Heat Piping...
Page 23: ...21 Figure 4 7 Recommended Domestic Hot Water Piping WATER PIPING AND CONTROLS...
Page 31: ...29 Figure 7 2 Wiring Schematic and Connection ELECTRICAL CONNECTIONS...
Page 45: ...E LIGHTING OPERATING PROCEDURES 43 START UP PROCEDURE...
Page 57: ...THIS PAGE INTENTIONALLY LEFT BLANK...
Page 60: ...58 REPAIR PARTS Figure 13 2 PBC 34 Combustion Components...
Page 62: ...60 REPAIR PARTS Figure 13 3 PBC 40 and PBC 52 Combustion Components...