G. INSTALLER MENU – 2000 LEVEL
The Installer Menu is accessible by inputting the proper
PIN number into screen CODE of the User Menu. When
CODE is the parameter selected press the M button. Use
the R1 and R2 buttons to select the proper number for
the flashing place in the PIN. Pressing M will advanced to
the next digit. If an incorrect number is selected, it is
required to cycle through all four places with the M button
to return and correct the number.
Once the 4 digit passcode has been entered, press L1 or
L2 until the menu selection screen is shown. Press R1 or
R2 until 2000 is shown in the small digits. Press M to
enter the Installer Menu
35
Table 8.7: Installer Menus (2000 Level)
Status
(2000)
Parameters
Parameter Function
Unit/Value
Default
Options
2001
Central Heat Mode
#
1
2003
CH Setpoint
°F
160
2005
CH Post Purge – Circulator
Seconds
10
2007
CH Hysteresis UP
– Controls Boiler shutoff point above Setpoint
°F
9
2009
Anti-cycling period
– Delay period during which boiler will not fire the burner if a supply temperature of CH
Se CH Hysteresis is reached during a single demand period.
Seconds
180
2010
Anti-cycling Differential
– Supply temperature drop below CH setpoint that must be reached before the burner will fire
if a supply temperature of CH Se CH Hysteresis is reached during a single demand
period.
– Overrides Anti-Cycling Period
°F
16
2014
Maximum CH Power
– Limits maximum CH input available to the control to satisfy a demand
– Default values should not be changed
%
PBC-34™: 57
PBC-40™: 61
PBC-52™: 54
2015
Minimum CH Power
– Limits the minimum power available to the boiler to satisfy a demand
%
1
2019
Boiler Supply Design Temperature
– Sets the reset curve design temperature that will be targeted when the outdoor temperature
is at the chosen outdoor design temperature.
– For default: Boiler will target 190°F when the outdoor temperature is 23°F or lower.
°F
190
2020
Outdoor Design Temperature
– Sets the Outdoor Temperature at which the boiler will target the Boiler Supply Design
Temperature.
– For default: Boiler will target 190°F when the outdoor temperature is 23°F or lower.
°F
23
2021
Boiler Mild Weather Temperature
– Sets the reset curve design temperature that will be targeted when the outdoor temperature
is at the Outdoor Mild Weather temperature.
– For default: Boiler will target 104°F when the outdoor temperature is 68°F.
°F
104
2022
Mild Weather Design Outdoor Temperature
– Sets the Outdoor Temperature at which the boiler will target the Boiler Mild Weather Design
Temperature.
– For default: Boiler will target 104°F when the outdoor temperature is 68°F.
°F
68
2023
Maximum CH Setpoint – Design Supply Maximum (limit)
– Sets upper limit of Calculated CH setpoint
– Calculated CH setpoint will always be at or below this value
°F
68
2024
Minimum CH Setpoint – Design Supply minimum (limit)
– Sets lower limit of Calculated CH setpoint
– Calculated CH setpoint will always be at or above this value
°F
190
BOILER CONTROL: INTERNAL WIRING & OPERATION
Installer Code is 0231
NOTICE
Summary of Contents for PBC-34
Page 22: ...20 WATER PIPING AND CONTROLS Figure 4 6 Recommended Central Heat Piping...
Page 23: ...21 Figure 4 7 Recommended Domestic Hot Water Piping WATER PIPING AND CONTROLS...
Page 31: ...29 Figure 7 2 Wiring Schematic and Connection ELECTRICAL CONNECTIONS...
Page 45: ...E LIGHTING OPERATING PROCEDURES 43 START UP PROCEDURE...
Page 57: ...THIS PAGE INTENTIONALLY LEFT BLANK...
Page 60: ...58 REPAIR PARTS Figure 13 2 PBC 34 Combustion Components...
Page 62: ...60 REPAIR PARTS Figure 13 3 PBC 40 and PBC 52 Combustion Components...