background image

TERMINAL HOUSING ASSEMBLY:

    For  aid  in 

installation the factory has pre-assembles the terminal 
housing (27) reducer tee (12) and compression coupling 
(13) together. This assembly also includes the 
suspension wires (18), electrodes (19) and fill-vent tee 
(5). 
 
Remove tape from and straighten the electrode wires. 
Remove kinks if necessary. Make sure all wires are 
marked. Wire “A” is the longest, wire “B” is the next 
longest, etc. 
 
Feed electrodes (19) and wires (18) into the Electrode 
Housing, being careful not to tangle or twist wires. Place 
terminal housing assembly on top of Electrode Housing 
(17) and press down on terminal housing assembly until 
pipe is inside of compression coupling (13). Hold the 
terminal housing in position and screw the cap on the 
compression coupling until the assembly is secured to 
the electrode housing (17). 
 
 

VENT:  

Atmospheric venting is required for this unit to 

operate.  In normal, non-explosive atmospheres, venting 
is accomplished via the small pierced hole in the metal 
closure installed in the side opening of the fill-vent tee.  If 
the terminal housing is to be installed in an explosive 
atmosphere, pry the metal closure from the tee and 
discard. The exposed vent opening should be connected 
to uncontaminated air by means of pipe or tubing. The 
opening is threaded behind the closure to accommodate 
a ¾” pipe fitting.  
 
 

CAUTION

 

Never block, plug or close off Vent openings. Inspect 
closure for presence of pierced hole and add if missing. 
This device will not function without venting. 
 
 

FILLING FLEXIBLE BULB:

 Fill the basin  with water to 

a level approximately 4” below the cap to which the bulb 
is attached. Remove the plug from the top of the fill-vent 
tee. Tee is located near the terminal housing. Pour in the 
electrolytic solution (a mixture of 3 ½ quarts of distilled 
water and one (1) package of sodium bicarbonate.) 
Replace the top plug. 
 

WARNING  

Before attempting repairs to  
installation, disconnect the power supply. Controls 
are automatic. This prevents accidental running of 
pump motor. Starting motor during repair activities 
could damage pump and may cause personal injury. 

 

WIRING: 

Remove the cover (1) from the terminal 

housing and install conduit from the housing to the 
control  box.   Use  14  AWG  wire  with  600  volts  rated 
insulation and 3/64 inch minimum insulation wall 
thickness to connect the letter coded wires to the 
indicated  terminals in the control box.  Be sure electric 
current is the same as that stamped on the control box 
nameplate.  Wire per wiring diagram supplied with 

control panel. If diagram is lost or misplaced copies may 
be obtained from your local Peerless Pump 
representative. 
 

NOTE:  When the Sealtrode Control Box is remotely 
located the distance from the SEALTRODE in the 
pumping station to the control box or panel    should not 
exceed 100 feet.   
Two separate metallic conduits are required from the 
pumping station to the building housing the control, one 
for the SEALTRODE r wires and one for the wires 
between the motors and controls. 
 
GENERAL: 

The installation of the controller is now 

completed and the level within the 1 ½” Electrode 
Housing will  faithfully   duplicate   the   liquid   level   in 
the  basin actuating  the  control  as  the  liquid  rises 
and falls and making and breaking contact with the 
electrodes. 
 
 

HOW TO ADJUST ELECTRODE SETTING: 

The 

electrode elevations have been pre-set at the factory 
and no further adjustment should be necessary. Should 
it be desirable, however, to readjust the factory settings 
refer to page 5 and note the assembly arrangement for 
anchoring the wires within the terminal housing. Also 
refer to page 5 and note and select the proper letter 
coded wire to be adjusted. 
 
To adjust electrode remove the terminal housing cover 
(1) and slowly loosen the compression fitting (8) just 
enough to be able to slide the selected suspension wire 
up or down as required. When adjustment has been 
made, re-tighten the compression fitting. 
 
There is sufficient suspension wire coiled inside the 
terminal housing to permit each electrode to be lowered 
a maximum of one foot, with the exception of the lowest 
electrode, which is the pump cut-out electrode with 
suspension wire labeled “A”. The low electrode wire 
marked “A” is already positioned near the bottom of the 
1 ½” Electrode Housing and should not be lowered 
further. This also applies to electrode wire mark A1 or 
A2.  
 

BELOW GRADE MOUNTING: 

When installing below 

grade make electrical connections above grade. There 
are 48 inches of suspension wire furnished past the 
terminal housing for below grade mounting. 
 

CAUTION

 

 

Do not allow the liquid leveling the basin to 

submerge the terminal housing. 
 
 

 
 
 
 

4848247

3

Summary of Contents for Sealtrode P Series

Page 1: ...y does not cover parts repaired outside the Seller s factory without prior written approval Seller makes no warranty as to starting equipment electrical apparatus or other material not of its manufacture since the same are usually covered by warranties of the respective manufacturers thereof Manufacturer and may also result in bodily injury as well as property damage This book is intended to be a ...

Page 2: ...use a good pipe thread compound to insure a watertight connection To protect and facilitate installation roll the flexible bulb into a compact bundle about its vertical axis and 4848247 2 Before attempting examination handling or repair be certain that the electrical power supply is shut off An electrical shock from contact with live wires or cards can be fatal Before opening the conduit box of an...

Page 3: ...4 AWG wire with 600 volts rated insulation and 3 64 inch minimum insulation wall thickness to connect the letter coded wires to the indicated terminals in the control box Be sure electric current is the same as that stamped on the control box nameplate Wire per wiring diagram supplied with control panel If diagram is lost or misplaced copies may be obtained from your local Peerless Pump representa...

Page 4: ...filled and the pumps do not cut off remove and empty the bulb and refill as outlined on page 3 under the heading Filling Flexible Bulb LOCATING TROUBLE IF THE PUMP FAILS TO START 1 Make sure sodium bicarbonate has been added to water 2 Check the electrical service making sure the current characteristics are the same as that stamped on the control box nameplate 3 Check to see if the control wiring ...

Page 5: ...DT 4848247 5 ...

Page 6: ...unted in enclosure for 1 phase motors only All mounted and pre wired in NEMA 1 general purpose or NEMA 4 watertight dead front enclosure 4848247 6 TYPE L and TYPE VCS PUMPS Fusible Disconnect Switch DY60FD Circuit Breaker DY60CB SERIES P DUPLEX COMBINATION SEALTRODE FLOATLESS CONTROLLER consists of A Electrode and terminal housing assembly including galvanized steel electrode housing NEMA 1 thru 4...

Page 7: ...or High Water Alarm Contacts Alarm Annunciation by others High Water Alarm with Annunciation Silencing Relay and Push Button Red High Water Alarm Light Enclosure Mounted Y 56 A U Y 56 A Simplex 2 X Y 57 A UH Y 57 A H Simplex 3 X X Y 57 AU A Y 57 A A Simplex 3 X Y 57 AU D Y 57 A D Duplex 3 X X Y 57 AU DH Y 57A DH Duplex 4 X X Y 57 AU DA Y 57 A DA Duplex 4 X Y 58 AU Y 58 A Duplex 3 X X Y 58 AU H Y 5...

Page 8: ...over Slotted Screw Upper Gasket 3 4 Pipe Plug 3 4 Tee 3 4 Nipple Ground Terminal Compression Fitting Phillips Head Screw Lower Gasket O Ring Reducer Coupling Compression Set Screw Sq Hd Mounting Flange Gasket Mtg Flg Electrode Hsg Suspension Wires Electrodes Bulb Adapter Hose Clamp Band Protector Bulb Housing Body Vent Cap 27 These parts make up the Terminal Housing 4848247 Rev 2 2 05 ...

Reviews: