background image

© COPYRIGHT 2010 PECO, INC.  ALL RIGHTS RESERVED.   

 

 

 

P/N 70476 3220-2265 REV 00 

7

taBle 2. aDvanceD conFIGUratIon (cont.)

menU

 

FeatUre

oPtIons

stD.moDel 

DeFaUlt

DescrIPtIon / comments

340

Keypad Lockout

0-3

0

Restricts access to certain features of device; Service Menu still available if enabled.

0 =   No key pad lockout (Default)

1 =   Disables Schedule and System keys

2 =   Disables Schedule, System, and Fan keys

3 =   Disables all keys

341

Enable Pin Access

0,1

0

Applies a 3 digit  access code to enter Service Menu 342

0 =  Disable,  

1 =   Enable

342

Set PIN Access 

Code

000-999

000

Choose a 3-digit code. 

350

Fan Mode 

Enable 

1-3

3

1 =    ON: Fan is turned on regardless of demand. 

2 =   Auto: Fan is turned on according to heating or cooling demand.

3 =   ON or Auto: Allows occupant to select either 1 or 2 above.

360

System Mode 

Enable

0-3

1

Allows ability to determine which system modes the occupant can select. 

0 =  OFF, Auto

1 =   OFF, Heat, Cool, Auto

2 =   OFF, Heat, Cool

3 =   Heat, Cool, Auto

380

Minimum Deadband 

Adjustment

3-10°F, 1.5-5°C

3°F 

Select a changeover deadband value to prevent short cycling between heating and cooling modes.  

The value is adjustable to meet various HVAC system requirements.

390

Pre-Occupancy 

Purge

0-3 hours

0 hours

Select to energize fan for selected number of hours (0-3) prior to all occupied events. 

395

Maximum Override 

Time Limit

0=Time until next 

event; or  

1-4 hours

3

Restricts the duration that a temporary hold can be set. The temporary hold is limited by the maximum 

amount of time as defined in this Service Menu. 

0 =   Remainder of time until the next scheduled event.

1 =   1 Hour

2 =   2 Hours

3 =   3 Hours

4 =   4 Hours

400

Cycles Per Hour 

(CPH)  

Cooling Stage 1

0-6 CPH 

3 CPH

Defines the number of cycles per hour for cooling (Stage 1). Select 0 to enable ON-OFF control for 

Stage 1 cooling.

410

Cycles Per Hour 

(CPH) 

Cooling Stage 2

0-6 CPH

3 CPH

Defines the number of cycles per hour for cooling (Stage 2). Select 0 to enable ON-OFF control for 

Stage 2 cooling.

420

Cycles Per Hour 

(CPH)  

Heating Stage 1

0-12 CPH

5 CPH

Defines the number of cycles per hour for heating (Stage 1). Select 0 to enable ON-OFF control for 

Stage 1 heating. 

430

Cycles Per Hour 

(CPH)  

Heating Stage 2

0-12 CPH

5 CPH

Defines the number of cycles per hour for heating (Stage 2). Select 0 to enable ON-OFF control for 

Stage 2 heating. 

450

Cycles Per Hour 

(CPH)   

Heating Stage 3

0-12 CPH

5 CPH

Defines the number of cycles per hour for heating. Select 0 to enable ON-OFF control for 

Heating Stage 3.

460

Heat Recovery Rate

0-18°F/Hr  

0-10°C/Hr

5°F/Hr

Defines the rate at which the device achieves the heat comfort setpoint. Select 0 to disable ramp 

recovery.

470

Cool Recovery Rate

0-18°F/Hr  

0-10°C/Hr

5°F/Hr

Defines the rate at which the device achieves the cool comfort setpoint. Select 0 to disable ramp 

recovery.

480

Minimum Off Time

1-10 minutes

4 minutes

Sets the minimum off time for both the heat and cool output.

490

Humidity Control 

Enable

(Select models only)

Selects how humidity will be controlled. When dehumidify control is enabled, the Y2 terminal becomes 

dehumidify.

0 =   Disabled

1 =   Dehumidify Control 

500

Programmable/ 

Intermittent Fan

0-2

0

0 =   Disable

1 =   Programmable Fan: Fan operates continuously in occupied periods or with demand in  

unoccupied periods. 

2 =   Intermittent Fan: Fan operates based on the on and off times set in menus 501 and 502.

Summary of Contents for Perfomance PRO T4500

Page 1: ...nd heat pump applications System mode selections Off Heat Cool Auto Stages 1 Heat 1 Cool 2 Heat 1 Cool 1 Heat 2 Cool 2 Heat 2 Cool 3 Heat 2 Cool Fan control Cycling Auto or Continuous On 1 Speed Permanent memory All device settings are stored in permanent memory Connections for Remote Sensors indoor and occupancy caUtIon 24 vac low voltage thermostat Do not install on voltages higher than 30 vac U...

Page 2: ... side 24 VAC sc Sensor Common sc Sensor Common s1 Indoor Remote Sensor s1 Indoor Remote Sensor System Type 1 1H 1C Conventional System Type 2 1H 1C Heat Pump TERM Function TERM Function C Common C Common W1 Heat B O Reversing Valve W2 AUX G Fan G Fan A A E E Y1 Cool Y1 Compressor Y2 Y2 RH Power for Heating RH Power for Heating RC Power for Cooling RC Power for Cooling System Type 3 Heat only witho...

Page 3: ...allplate Assure that the metal jumper connects RC and RH Connect power side to the RC RH and assure that the jumper remains in place two transformer system The T4000 T4500 is shipped with a jumper connecting terminals RH and RC If the heating and cooling equipment do not use separate transformers leave this jumper in place If separate transformers are required remove this jumper With the jumper re...

Page 4: ...wIth sYstem tests System test verification is highly recommended to verify thermostat operation Follow at least one procedure in the system tests below Refer to the Service Menus see Table 2 for more tests For all tests press next to continue to the following system test which is the next available Service Menu Press Done only if finished performing all system tests Pressing Done exits the Service...

Page 5: ...ostat press the lower left and lower right keys simultaneously for about five seconds Next Go Back and Done appear see Fig 14 2 Press Next until Service Menu 341 Enable Disable PIN Access appears in the display Default value 00 appears below Service Menu 3 In Service Menu 341 press to change digit flashing value to 01 see Fig 14 note selecting 01 enables PIn access for the thermostat service menus...

Page 6: ...ntrols heating fan 130 Changeover valve B O terminal 0 1 0 0 B O terminal controls valve in cooling 1 B O terminal controls valve in heating 140 Auxiliary Heat 0 1 0 0 Electric backup heat 1 Fossil fuel backup heat 150 Backlight 0 1 0 0 Backlight temporarily on 1 Backlight always on low intensity 24V only 170 Remote Sensor 0 1 0 Select sensor if used connected to the S1 Terminal Contact PECO for m...

Page 7: ...eduled event 1 1 Hour 2 2 Hours 3 3 Hours 4 4 Hours 400 Cycles Per Hour CPH Cooling Stage 1 0 6 CPH 3 CPH Defines the number of cycles per hour for cooling Stage 1 Select 0 to enable ON OFF control for Stage 1 cooling 410 Cycles Per Hour CPH Cooling Stage 2 0 6 CPH 3 CPH Defines the number of cycles per hour for cooling Stage 2 Select 0 to enable ON OFF control for Stage 2 cooling 420 Cycles Per H...

Page 8: ...Disable 1 Enable Note Press Done key to complete process 600 System Test Main Output Cool 0 2 0 Select an option to activate the fan output for 10 minutes select 0 Done or a different Service Menu to disable 0 Disable Default 1 Cool Stage 1 2 Cool Stage 2 610 System Test Main Output Heat 0 3 0 Select an option to activate the fan output for 10 minutes select 0 Done or a different Service Menu to d...

Page 9: ...resent check wire connection between the heating equipment and the thermostat If Demand Indicator light is red Heating is occurring No action is required If Demand Indicator light is green Cooling is occurring No action is required If Demand Indicator light is flashing An error has occurred Remote sensor may be malfunctioning Check remote sensor wiring Verify that the sensor s are PECO supported p...

Page 10: ...Unt Peco InDoor remote zone sensor sP155 017 warnInG READ THESE INSTRUCTIONS CAREFULLY BEFORE ATTEMPTING TO INSTALL OPERATE OR SERVICE THIS SENSOR Failure to observe safety information and comply with instructions could result in PERSONAL INJURY DEATH AND OR PROPERTY DAMAGE To avoid electrical shock or damage to equipment disconnect power before installing and use only wiring with insulation rated...

Page 11: ...sor maXImUm lenGth anD wIre sIze Distance from Unit to control recommended wire size 000 150 feet 22 gauge 151 240 feet 20 gauge 241 385 feet 18 gauge 386 610 feet 16 gauge 611 970 feet 14 gauge wIrInG 1 run wires Run wires between the thermostat wallplate and the Zone Sensor subbase 2 connect wires Connect the wiring to the terminals S1 and SC at the thermostat wallplate see Fig 22 note See TABLE...

Page 12: ...or message If the Indoor Remote Zone Sensor is not connected properly check the following Make sure sensor is wired properly and connected to terminals S1 and SC on the thermostat wallplate see Table 1 Terminal Designations and System Types If using multiple sensors make sure wiring follows diagrams in Sensor Wiring for Temperature Averaging Make sure to select 01 in Service Menu 170 Figure 25 The...

Reviews: