Peco Perfomance PRO T4500 Installation Manual Download Page 3

© COPYRIGHT 2010 PECO, INC.  ALL RIGHTS RESERVED.   

 

 

 

P/N 70476 3220-2265 REV 00 

3

System Type 9: 1H/2C Conventional

System Type 10: 2H/2C Heat Pump

TERM

Function

TERM

Function

C

Common

C

Common

W1

Heat

B/O

Reversing Valve

W2

AUX

G

Fan

G

Fan

A

A

E

E

Y1

Cool 1

Y1

Compressor 1

Y2

Cool 2

Y2

Compressor 2

RH

Power for Heating

RH

Power for Heating

RC

Power for Cooling

RC

Power for Cooling

System Type 11: 3H/2C Heat Pump 
TERM

Function

C

Common

B/O

Reversing Valve

AUX

Auxiliary Heat

G

Fan

A
E

Y1

Compressor 1

Y2

Compressor 2

RH

Power for Heating 

RC

Power for Cooling

Part II: attach wIres to thermostat wallPlate (cont.)

2.  Using a small fl athead screwdriver, loosen the screws on the terminal blocks that 

correspond to the system type (see Table 1 ). 

3.  Strip the insulation of each wire at a proper length (about 1/4” or 64 cm).

4.  On the wallplate, insert wires into the terminal blocks that correspond to the system 

type, then re-tighten each screw for each terminal (see Fig. 4).

note: Do not over-tighten screws or use excessive force.  

5.  Assure that no uninsulated wires are exposed: Cap off and place a wire-nut on any 

unused wires. Assure that the attached wires fi t into the cavity on the back side of the 

thermostat. 

Part III: connect Power to the thermostat

1.  Choose from the following options to power the thermostat. 

Power options

The Performance PRO T4000 Series will operate on 24VAC power and/or two AA 

batteries (both are recommended).   Choose from three methods to connect power to the 

thermostat. 

• Batteries only (AA alkaline)

• 24 VAC direct connection only

• 24 VAC with AA battery backup (highly recommended)

wiring 24 vac common

• single-transformer system

: Connect the common side of the transformer to 

the “C” screw terminal of the thermostat wallplate. Assure that the metal jumper 

connects “RC” and “RH.” Connect power side to the RC/RH and assure that the 

jumper remains in place. 

• two-transformer system:

 The T4000/T4500 is shipped with a jumper connecting 

terminals RH and RC. If the heating and cooling equipment do not use separate 

transformers, leave this jumper in place. If separate transformers are required, 

remove this jumper. With the jumper removed, connect RC to the power side of the 

cooling transformer. Connect RH to the power side of the heating transformer; then 

connect both the heating and cooling commons together to terminal C (Common). 

Part Iv: Install BatterIes

Insert two AA batteries (included) into the back compartment of the thermostat, where 

indicated (see Fig. 5). 

Part v: set the clock, month, anD DaY

When power is fi rst applied to the thermostat, it will activate the clock display. It 

is recommended that the time and day are entered before performing advanced 

confi guration. Follow the procedure below to set the clock, month, and day (see Fig. 6). 

1.  Press ▲/ ▼ to select 12 or 24 HR mode, then press 

Next.

2.  Press ▲/ ▼to select clock hour, then press 

Next

.  

3.  Press ▲/▼to select clock minutes, then press 

Next

4.  Press ▲/ ▼ to select clock year, then press 

Next

5.  Press ▲/ ▼ to select current month, then press 

Next

note

Mo

 (month) appears.

6.  Press ▲/ ▼to select current date. 

note

Days

 appears. 

7.  Press 

Done

 to fi nish clock mode. 

Part vI: verIFY sYstem settInG Is tUrneD oFF

1.  Press any key to enter the Home Display.

2.  Press 

System

 to enter system settings. 

3.  Press ▲/ ▼to select “Off,” then press 

Done

4.  Press 

Fan

 key to enter fan mode. 

5.  Press ▲/ ▼to select “Auto,” then press Done. 

note: the fl ashing option is the selection. 

Figure 5. 

Insert two AA batteries  

in back of thermostat.

Figure 4. 

Insert wires into 

appropriate terminal 

blocks.

Enlarged area 

shows wire 

insertion point 

above terminal 

block

• 

caUtIon: Do not connect 

unused wires together.

▲ 

!

Figure 6.

Clock must 

be set before 

performing  

advanced 

confi guration. 

Summary of Contents for Perfomance PRO T4500

Page 1: ...nd heat pump applications System mode selections Off Heat Cool Auto Stages 1 Heat 1 Cool 2 Heat 1 Cool 1 Heat 2 Cool 2 Heat 2 Cool 3 Heat 2 Cool Fan control Cycling Auto or Continuous On 1 Speed Permanent memory All device settings are stored in permanent memory Connections for Remote Sensors indoor and occupancy caUtIon 24 vac low voltage thermostat Do not install on voltages higher than 30 vac U...

Page 2: ... side 24 VAC sc Sensor Common sc Sensor Common s1 Indoor Remote Sensor s1 Indoor Remote Sensor System Type 1 1H 1C Conventional System Type 2 1H 1C Heat Pump TERM Function TERM Function C Common C Common W1 Heat B O Reversing Valve W2 AUX G Fan G Fan A A E E Y1 Cool Y1 Compressor Y2 Y2 RH Power for Heating RH Power for Heating RC Power for Cooling RC Power for Cooling System Type 3 Heat only witho...

Page 3: ...allplate Assure that the metal jumper connects RC and RH Connect power side to the RC RH and assure that the jumper remains in place two transformer system The T4000 T4500 is shipped with a jumper connecting terminals RH and RC If the heating and cooling equipment do not use separate transformers leave this jumper in place If separate transformers are required remove this jumper With the jumper re...

Page 4: ...wIth sYstem tests System test verification is highly recommended to verify thermostat operation Follow at least one procedure in the system tests below Refer to the Service Menus see Table 2 for more tests For all tests press next to continue to the following system test which is the next available Service Menu Press Done only if finished performing all system tests Pressing Done exits the Service...

Page 5: ...ostat press the lower left and lower right keys simultaneously for about five seconds Next Go Back and Done appear see Fig 14 2 Press Next until Service Menu 341 Enable Disable PIN Access appears in the display Default value 00 appears below Service Menu 3 In Service Menu 341 press to change digit flashing value to 01 see Fig 14 note selecting 01 enables PIn access for the thermostat service menus...

Page 6: ...ntrols heating fan 130 Changeover valve B O terminal 0 1 0 0 B O terminal controls valve in cooling 1 B O terminal controls valve in heating 140 Auxiliary Heat 0 1 0 0 Electric backup heat 1 Fossil fuel backup heat 150 Backlight 0 1 0 0 Backlight temporarily on 1 Backlight always on low intensity 24V only 170 Remote Sensor 0 1 0 Select sensor if used connected to the S1 Terminal Contact PECO for m...

Page 7: ...eduled event 1 1 Hour 2 2 Hours 3 3 Hours 4 4 Hours 400 Cycles Per Hour CPH Cooling Stage 1 0 6 CPH 3 CPH Defines the number of cycles per hour for cooling Stage 1 Select 0 to enable ON OFF control for Stage 1 cooling 410 Cycles Per Hour CPH Cooling Stage 2 0 6 CPH 3 CPH Defines the number of cycles per hour for cooling Stage 2 Select 0 to enable ON OFF control for Stage 2 cooling 420 Cycles Per H...

Page 8: ...Disable 1 Enable Note Press Done key to complete process 600 System Test Main Output Cool 0 2 0 Select an option to activate the fan output for 10 minutes select 0 Done or a different Service Menu to disable 0 Disable Default 1 Cool Stage 1 2 Cool Stage 2 610 System Test Main Output Heat 0 3 0 Select an option to activate the fan output for 10 minutes select 0 Done or a different Service Menu to d...

Page 9: ...resent check wire connection between the heating equipment and the thermostat If Demand Indicator light is red Heating is occurring No action is required If Demand Indicator light is green Cooling is occurring No action is required If Demand Indicator light is flashing An error has occurred Remote sensor may be malfunctioning Check remote sensor wiring Verify that the sensor s are PECO supported p...

Page 10: ...Unt Peco InDoor remote zone sensor sP155 017 warnInG READ THESE INSTRUCTIONS CAREFULLY BEFORE ATTEMPTING TO INSTALL OPERATE OR SERVICE THIS SENSOR Failure to observe safety information and comply with instructions could result in PERSONAL INJURY DEATH AND OR PROPERTY DAMAGE To avoid electrical shock or damage to equipment disconnect power before installing and use only wiring with insulation rated...

Page 11: ...sor maXImUm lenGth anD wIre sIze Distance from Unit to control recommended wire size 000 150 feet 22 gauge 151 240 feet 20 gauge 241 385 feet 18 gauge 386 610 feet 16 gauge 611 970 feet 14 gauge wIrInG 1 run wires Run wires between the thermostat wallplate and the Zone Sensor subbase 2 connect wires Connect the wiring to the terminals S1 and SC at the thermostat wallplate see Fig 22 note See TABLE...

Page 12: ...or message If the Indoor Remote Zone Sensor is not connected properly check the following Make sure sensor is wired properly and connected to terminals S1 and SC on the thermostat wallplate see Table 1 Terminal Designations and System Types If using multiple sensors make sure wiring follows diagrams in Sensor Wiring for Temperature Averaging Make sure to select 01 in Service Menu 170 Figure 25 The...

Reviews: