background image

Flow rate                 gpm 

10 

15 

18 

20 

25 

30 

35 

40 

Best control 1 ¼’’ psi loss 

0.5  1.5  2.5  3.5  5.5  7.5 

10  12.5 

Best control 1’’     psi loss  0.5  1.5 

6.5  8.5 

Use BEST CONTROL 1” in a bypass when friction loss is excessive. 

Flow rate                            gpm  20 

30 

40 

50 

60 

70 

80 

Best control 1” x 1’’    psi loss 

14 

19 

Best control 1” x 1 ¼’’psi loss 

10 

12 

Best 

control 

1” 

½’’psi 

loss 

2 2 3 4 6 7 8 

Pressure Loss Chart with a bypass application with Best control 1” * 

PRESSURE  LOSS   -   BYPASS APPLICATION

- 8 - 

BEST CONTROL 1” 

Gauge 

1’’ 

1’’ 

Gate valve 

Spring check valve 

System pipe 

System pipe 

The main pipe of bypass must not exceed 1 1/2”, while the system pipe could be bigger. 

Main pipe bypass 

1’’,   1 ¼’’,   1 ½’’ 

* Available on request. 

Pressure Loss Chart 

Summary of Contents for PCBC16F16S

Page 1: ...Built in pressure and flow switch Can be used with or without pressure tank e m i t d n a e c a p s s e v a s n o i t a l l a t s n i e l p m i S e v l a v k c e h c n i t l i u B d e r i u q e r e c...

Page 2: ...nnections 9 Installation wiring diagram 115 VAC 2 wire pumps up to 16 FLA 9 Installation wiring diagram 230 VAC 2 wire pumps up to 20 FLA 10 Installation wiring diagram 230 VAC 3 wire pumps up to 20 F...

Page 3: ...m and disconnect power supply before installing or servicing BEST CONTROL Make sure line voltage and frequency of power supply match motor nameplate voltage and frequency and BEST CONTROL voltage and...

Page 4: ...p opened Green Power on light and yellow Pump on should display This indicates system is operating properly If red Failure light comes back on refer to Troubleshooting Guide OPERATION TROUBLESHOOTING...

Page 5: ...he six screws from the cover Line voltage and pump wires to the BEST CONTROL should be supplied through liquid tight nonmetallic conduit fittings rated NEMA 12 or UL type 12 to achieve NEMA Type 12 en...

Page 6: ...PS 5 If pressure exceeds 145 psi install a pressure reducing valve ABOVE GROUND PUMP BEST CONTROL can be installed on above ground and submersible pumps for residential domestic irrigation and booster...

Page 7: ...vel Do not install any tap or tee between the pump and the BEST CONTROL Install a pressure reducing valve between pump and BEST CONTROL when maximum pressure generated by the pump exceeds 145 psi Inst...

Page 8: ...st tap must not exceed 70 feet BEST CONTROL unit operates from min 32 psi to the max pressure generated by the pump C BEST CONTROL preset cut in pressure 42 psi model Max pressure generated by the pum...

Page 9: ...rol 1 x 1 psi loss 3 5 9 14 19 Best control 1 x 1 psi loss 2 2 3 5 8 10 12 Best control 1 x 1 psi loss 2 2 3 4 6 7 8 Pressure Loss Chart with a bypass application with Best control 1 PRESSURE LOSS BYP...

Page 10: ...licable BEST CONTROL wiring diagram If pump motor FLA exceeds BEST CONTROL rating use magnetic starter wiring diagram for the applicable voltage see pages 12 13 Use Copper Conductors only Use 140 167...

Page 11: ...INSTALLATION WIRING DIAGRAM 230VAC 2 WIRE PUMPS UP TO 20 FLA INSTALLATION WIRING DIAGRAM 230VAC 3 WIRE PUMPS UP TO 20 FLA 10...

Page 12: ...ase applications Remember match coil voltage on contactor with BEST CONTROL voltage Either 115V or 230V coils may be used Use of magnetic starter to avoid damage to the device is determined by pump mo...

Page 13: ...R 230 VAC THREE PHASE 3 WIRE PUMPS INSTALLATION WIRING DIAGRAM 460VAC For 460Vac motors use magnetic starter to avoid damage to BEST CONTROL 12 For 208Vac or 230Vac three phase motors use magnetic sta...

Page 14: ...OVERALL DIMENSIONS 13 INSTALLATION WIRING DIAGRAM 230VAC 3 WIRE PUMPS EXCEEDING 20 FLA...

Page 15: ...ill not operate WARNING Do not turn on power until the box cover has been securely fastened 4 Install the new electronic box and t ighten the three screws Do not overthighten or damage to threads may...

Page 16: ......

Reviews: