52
Harmonics of AC Current in Percentage
(1 to 99
th
order. Min. current at 50 or 60 Hz is:
3&(
830+
3&(
6801 > 10% of the
range;
3&(
830+
3&(
6802 > 20A;
3&(
830+
PCE-
3007 > 30A. If the current
is 0 at 50 or 60 Hz, all the percentage (%) display is 0)
PCE-
830+
PCE-
6801
Range Resolution
Accuracy
1 – 10
th
±0.2% of reading ± 1%
11 – 20
th
±2% of reading ± 1%
21 – 50
th
(A range)
±5% of reading ± 1%
21 – 50
th
(mA range)
±10% of reading ± 1%
51 - 99
th
0.1%
±35% of reading ± 1%
PCE-
830+
PCE-
6802
Range Resolution
Accuracy
1 – 20
th
±2%
21 – 49
th
±4% of reading ± 2.0%
50 – 99
th
0.1 %
±6% of reading ± 2.0%
PCE-
830 +
PCE-
3007
Range Resolution
Accuracy
1 – 20
th
0.1%
±2%
21
st
– 50
th
0.1%
±6%
51
st
– 99
th
0.1%
±10%
Harmonics of AC Current in Magnitude
(1 to 99
th
order. Min. current at the 50 or 60 Hz:
3&(
830+
3&(
6801 > 10% of the
range;
3&(
830+
3&(
6802 > 20A. CT=1)
PCE-
830+
PCE-
6801
Range Resolution
Accuracy
1 – 10
th
±0.2% of reading ±7dgts
11 – 20
th
±2% of reading ±7dgts
21 – 50
th
(A range)
±5% of reading ±7dgts
21 – 50
th
(mA range)
±10% of reading ±7dgts
51 - 99
th
0.1mA / 0.1A
±35% of reading ±7dgts
PCE-
830+
PCE-
6802
Range Resolution
Accuracy
1 – 20
th
±2% of reading ±0.4A
21 – 49
th
±4% of reading ±0.4A
50 – 99
th
0.1A
±6% of reading ±0.4A
(1 to 99
th
order, min. current at the 50 or 60 Hz, True RMS < 300A for 3007, True
RMS )