4 Disposal
2020/03
99703601-mub-ml – V02
9
3.1
Technical data
TECHNICAL DATA PKR6
Dimensions
95 x 80.3 x 91.2 mm³
Sense of rotation
selectable in the menu
Power supply
230 V~, 50 Hz
Runtime
120 s
Own consumption
max. 3 VA
Torque
6 Nm
Protection class
I acc. to EN 60730-1
Manual operation
Gear disengagement
Protection level
IP42 acc. to EN 60529
Maintenance
maintenance-free
Admissible ambient
temperature
0 °C . . . + 50 °C
TECHNICAL DATA SENSOR
Admissible relative
humidity
max. 85 % RH at 25 °C
Admissible temperature
sensor type
Pt-1000
Rotation angle
90°, electrically limited
Sensor resistance
1078 ohms at 20 °C
Programme class
A
Application range
sensor
-25 °C . . . +150 °C
Data storage without
power supply
min. 10 years
Conductor cross section
for sensor connection
min. 0.3 mm²
Connection cable with
plug
2 m, 3 x 0.75 mm²
Length of sensor cable max. 10 m
4
Disposal
Possibilities to return waste electrical and electronic equipment
Waste electrical and electronic equipment deriving from private households
can be disposed at collection points of the public waste management
authorities or at disposal points set up by manufacturers or distributors
according to the ElektroG (Electrical and Electronic Equipment Act).
You find an online directory of all collection and disposal points here:
https://www.ear-system.de/ear-verzeichnis/sammel-und-
ruecknahmestellen.jsf
Disposal of transport and packaging materials
The packaging materials are made of recyclable materials and can be disposed of with