The thermostat switches on and off one or more loads (e.g. heated drinking bowls) up to a total load of 16A
(2.5 A with motor load).
This is important for the operation of heating drinking systems, so that the heating is switched on immediately in the
case of frost. Otherwise the heating is switched off when the set temperature values are reached. The thermostat is
resistant against ammoniacal steam, such as stable air. The set value (scale value) is adjusted at the rotary switch.
The sensor must be able to notice all temperature influences. It should be placed with plenty of air circulation, not in
"dead" corners or in the vicinity of cooling or heating areas or windows. Direct sunlight should be avoided. The
temperature sensor and the unit should be cleaned regularly.
After removing the rotary switch and the upper cover, fix the unit to the wall. It‘s only usable for connecting to
permanently installed lines.
Errors in the connection can damage the unit! No liability is accepted for damage caused by incorrect
connection and/or improper handling!
Before working on the unit, make sure all cables are voltage free! The connection must only be made by authorised
expert personnel! Connect the unit as shown on the enclosed simplified diagram. The VDE 0100, especially parts 705
and EN 60730 (part 1), have to be considered. If the unit does not work, first check the connection and the power
supply.
Application, function, operation
Positioning, maintenance
Mounting
Dimensions
1.
2.
3.
4.
Protection class IP 54
Wall mounting
Individual limitation of
the control range