background image

4.1.3  4-WIRE CONNECTION USING TERMINAL BLOCKS 

If your RS-485 application requires you to connect two pairs of bare

wires to the Model 2085, you will need to open the case to access the
terminal blocks.  The following instructions will tell you how to open the
case, connect the bare wires to the terminal blocks, and fasten the
strain relief collar in place so that the wires won't pull loose.

1.  You should already have the case open for the configuration

procedure.  If not, open the case according to the diagram in Section
3.2.   

2.  Strip the outer insulation from the twisted pairs about one inch

from the end.  

3.  Strip back the insulation on each of the 2 twisted pair wires

about .25".

4.  Connect 

one pair

of wires to XMT+ and XMT- (transmit positive

and negative) on the terminal block, making careful note of which color
is positive, and which color is negative.  

5. Connect the 

other pair

of wires to RCV+ and RCV- (receive

positive and negative) on the terminal block, again making careful note
of which color is positive, and which color is negative.

Ultimately, you will want to construct a two pair cross over cable that

makes a connection with the RS-485 device as shown below:

Model 2085

RS-485 Device

XMT+.............................RCV+
XMT-..............................RCV-

RCV+.............................XMT+
RCV-..............................XMT-

11

3.3  DIP SWITCH SETTINGS

All possible settings for the Model 2085’s configuration switches

are presented in Figure 5 (below).  Following Figure 5 is a detailed
description of each switch function.  If you have additional questions,

contact Technical Support at (301) 975-1000.

*Note: 

Switches S1-1 & S1-2 should be switched simultaneously.

Switches S1-7 & S1-8 should also be switched simultaneously.

S1-1 and S1-2:  “Transmit Off” Impedance

Switches S1-1 and S1-2 are set together to determine whether the

receiving device “sees” the impedance of the Model 2085’s transmitter
as being “high” or “intermediate” when the transmitter is turned off.  The 
“intermediate” setting is useful in half-duplex environments where the
receiving device does not respond well to the “high” setting.

S1-1

S1-2

Setting

On

On

Intermediate Impedance

Off

Off

High Impedance

S1-3:  RTS/CTS Delay

The setting for switch S1-3 determines the amount of delay

between the time the Model 2085 “sees” RTS and when it sends CTS.

Note

:  RTS/CTS Delay setting should be based upon transmission

timing.

S1-3

Setting

On

8 mSec

Off

no delay

6

S1 SUMMARY TABLE

Position

Function

Factory Default

S1-1*

“Transmit Off” Impedance

Off

S1-2*

“Transmit Off” Impedance

Off

S1-3

RTS/CTS Delay

On

8 msec

S1-4

“ECHO” Mode

Off

Echo Off

S1-5

Carrier Control

On

RTS Cont.

S1-6

Receive Impedance

On

120 Ohm

S1-7*

2-Wire/4-Wire

On

S1-8*

2-Wire/4-Wire

On

High Z

2-Wire

}

Figure 5.

Summary of DIP switch default settings for set S1

}

Summary of Contents for 2085

Page 1: ...CE 301 975 1000 TECHNICAL SUPPORT 301 975 1007 http www patton com Part 07M2085 D Doc 047033U Rev E Revised 1 22 08 MODEL 2085 High Speed RS 232 to RS 485 Interface Converter C E R T I F I E D An ISO...

Page 2: ...d used properly that is in strict accordance with the manufacturer s instructions may cause interference to radio and television reception The Model 2085 has been tested and found to comply with the l...

Page 3: ......

Page 4: ...relief RJ 11 or RJ 45 Silicon Avalanche Diode surge protection 2 2 DESCRIPTION The Model 2085 High Speed RS 232 to RS 485 Interface Converter provides exceptional versatility in a compact package Requ...

Page 5: ......

Page 6: ...he Model 2085 to behave like Data Communications Equipment and transmit data on pin 3 3 2 DIP SWITCH CONFIGURATION The eight switches on switch set S1 see Figure 3 above configure the Model 2085 for e...

Page 7: ......

Page 8: ...etting On Controlled by RTS Off Constantly On S1 6 Receive Impedance The setting for switch S1 6 selects the impedance of the input receiver You may select either a low impedance of 120 Ohms or a high...

Page 9: ......

Page 10: ...available with several different physical interfaces on the RS 485 side DB 25 following the RS 520 standard RJ 11 jack RJ 45 jack and terminal blocks with strain relief 4 1 1 4 WIRE CONNECTION USING T...

Page 11: ......

Page 12: ...n Section 3 2 2 Strip the outer insulation from the twisted pairs about one inch from the end 3 Strip back the insulation on each of the 2 twisted pair wires about 25 4 Connect one pair of wires to XM...

Page 13: ......

Page 14: ...ptive screw through a saddle washer and then insert the captive screw with the washer on it through the hole in the DB 25 end of the case Snap that side of the case closed Repeat the process for the o...

Page 15: ......

Page 16: ...e DB 25 port of the RS 232 device Remember to insert and tighten the two captive connector screws Note If you must use a cable to connect the Model 2085 to the RS 232 device make sure it is a straight...

Page 17: ......

Page 18: ...From Model 2085 7 SG Signal Ground 8 DCD Data Carrier Detect From Model 2085 To Model 2085 Data Term Ready DTR 20 DIRECTION DCE SETTING DIRECTION 1 FG Frame Ground 2 TD Transmit Data From Model 2085 3...

Page 19: ......

Page 20: ......

Reviews: