background image

8.

Replace the spare fuse with one of the appropriate size and rating
and close the drawer.

9.

Re-install the power cord.

(Step #6- 9 for Model 1000RPEM-V)

6.

Using a small screwdriver, push in lightly and turn counter
clockwise to open the compartment.  The top will pop open with the
fuse attached. 

7.

If the active fuse appears to be blown, remove it from the front
container.  Note the size and rating of the blown fuse before
discarding (*120V = TO.4; 240V = TO.2).

8.

Replace the spare fuse with one of the appropriate size and rating
and close the compartment.

9.

Re-install the power cord.

APPENDIX A

SPECIFICATIONS

1000RPSM-2 and 1000RPSM-V (AC Front Cards):

Power Supply:  120V AC or 220-24V AC, switchable

Input Voltage:  “120V AC” setting: 100-130V AC;  “220V AC” setting:

200-240V AC

Maximum Input Current:  “120V AC” setting: 400mA;  “220V AC”

setting: 200mA

Isolation Voltage:  Model 1000RPSM-2: 1.5 kV AC;

Model 1000RPSM-V: 5 kV AC

Output Voltage:  10V AC @ 2.4 A

Output Power:  24VA

Switches:  Power on/off

LED Indicator: Power

1000RPEM and 1000RPEM-V (AC Rear Cards):

Connection:  IEC-320 Shrouded Male

Fuse:  120V AC:  5x20mm, 400mA, Time-Delay; 240V AC: 5x20mm,

200mA, Time-Delay

WARNING!

Replace the fuse only with one that has

the correct voltage and current rating for the voltage
setting of the unit (the proper fuse ratings will be marked
on the rear panel of the unit*).  Replacing the fuse with
one having an incorrect rating can result in a fire!

9

10

Summary of Contents for 1000RP Series

Page 1: ...USER MANUAL Model 1000RP Series AC and DC Rack Mount Power Supplies SALES OFFICE 301 975 1000 TECHNICAL SUPPORT 301 975 1007 Part 07M1000RP B Doc 078011UB Revised 3 19 96...

Page 2: ...on the outside of the shipping container This number may be obtained from Patton Electronics Technical Service at 301 975 1007 Packages received without an RMA number will not be accepted Patton s te...

Page 3: ...Chassis Figure 1 below features sixteen function card slots and one power supply card slot Note refer to function card user manuals for proper installation of function cards Measuring only 3 5 high th...

Page 4: ...wer switch is turned on and low voltage AC power is available to the function cards installed in the rack The DC Input LED will light whenever a power source is present with correct polarity regardles...

Page 5: ...OFF 2 Remove the power plug from the AC wall outlet 3 Remove the power plug out of the rear of the unit 4 Switch the unit ON and verify that the front panel Power LED is not lit Switch the unit OFF 5...

Page 6: ...1000RPSM 2 and 1000RPSM V AC Front Cards Power Supply 120V AC or 220 24V AC switchable Input Voltage 120V AC setting 100 130V AC 220V AC setting 200 240V AC Maximum Input Current 120V AC setting 400mA...

Page 7: ...d Connection Cage clamp terminal block with DC In DC In Frame Ground Alarm Alarm C DC Out DC Out Wire 26 14 solid or stranded cable Alarm Opens when power is attached and closes when power is disconne...