4 Operations
4.1 NURO
®
Control Panel
Once the boiler has been installed in compliance with this
manual, it is necessary to open the front door of the boiler in
order to access the power (on/off) switch located in the upper
right hand corner of the NURO
®
control panel as shown below:
NURO Touch Screen Interface
Once the boiler is switched to the “ON” position, the P-K SOLIS boiler
can be programmed and operated with the NURO
®
touch screen
interface located on the front door as shown to the right. A clear
plastic cover protects the touch screen which can be opened by
pinching the clasp and swinging open to the left.
Factory Tests
Safe lighting and other performance criteria were met with the gas
manifold and control assembly provided
on this boiler when the boiler
underwent factory tests specified in ANSI Z21.13/CSA
4.9, latest
edition. (See "Factory
Firetest" label on the rear surface of the boiler).
Do not use this boiler if any part
has been under water.
Immediately call a qualified
service technician to inspect the
boiler and to replace any part of
the control system and any gas
control which has been under
water. Failure to do so could
result in electrocution, injury, or
death.
If overheating occurs or the gas
supply fails to shut off, do not
turn off or disconnect the
electrical supply to the pump.
Instead, shut off the gas supply at
a location external to the boiler.
N
OTICE
!
The On/Off switch only interrupts
power to the NURO
®
control
system. In order to fully remove
power to the entire boiler, use
the external disconnect.