Auxiliary Input #1
–
The TB2-7 & TB2-8 terminals are used for Auxiliary Input #1. This circuit is
energized with 120VAC
.
Auxiliary Input #2
–
The TB2-9 & TB2-10 terminals are for Auxiliary Input #2. This circuit is energized
with 120VAC
.
Air Damper Interlock
– The Air Damper Interlock TB2-9 & TB2-10 terminals
allow for proof of open
end limit switch on a motorized air damper. This circuit is energized with 120VAC, so the contacts on
the end limit switch must be rated for minimum 120VAC. The appliance ships with a factory-installed
jumper across the Air Damper Interlock terminals. Remove the jumper if connecting a motorized air
damper with end limit switch.
Ground
– Grounding connection for auxiliary safety/limit devices on terminals TB2-11 & TB2-12.
Relay A, B, C & D
– User-configurable relay outputs A (TB2-19 & TB2-20), B (TB2-17 & TB2-18), C
(TB2-15 & TB2-16) & D (TB2-13 & TB2-14). The normally-open contacts on these relays have a
maximum voltage rating of 240VAC and maximum current capacity of 1/2 Amp.
Master Alarm Relay
– The Master Alarm Relay TB2-21 & TB2-22 terminals are normally-open dry
contacts that close in the event of an alarm output from the NURO control. The normally-open contacts
on this relay have a maximum voltage rating of 240VAC and maximum current capacity of 1/2 Amp.
NOTE:
The Start Interlock circuit must close within 5 minutes of a call for heat. Failure to close the
Start Interlock circuit will cause the appliance to lockout on alarm.
NOTE:
The boiler ships with a factory-installed jumper across the Air Damper Interlock terminals.
Remove the jumper if connecting a motorized air damper with end limit switch.
NOTE:
This ground terminal is connected to the TB2 sheet metal and is not common with the
appliance’s electrical service ground.
NOTE:
Refer to
6.1
or proper
wiring and configuration of the electrical connections. Relays A
through D can be user-configured through the NURO
®
touch screen interface to control devices
such as the Comfort Heat (CH) pump, Domestic Hot Water (DHW) Pump, Air Damper, System
Pump, etc.