background image

 

Zone(s) Not Calling 

Each zone has a Green LED next to the zone relay when it is 
calling. The LED being lit shows that the call is being recognized by 
the PCMMP3. If a zone is supposed to be calling and the Zone LED 
is not on, check for 24VAC across the thermostat terminal C and the 
Y, if a Cool call, W if a Heat Call, or G if a Fan call. If there is no 
voltage here at the panel the panel is not getting the signal from the 
thermostat. The problem is mis-wiring, a broken wire or a problem in 
the thermostat. To check the zone on the panel, place jumper from 
R to Y to simulate a Cool call, R to W to simulate a Heat call, or R to 
G to simulate a Fan call. By jumpering these terminals the zone call 
LED will activate.     
 

Zone(s) Will Not Shut Off 

If a zone will not stop calling, the Zone LED should still be on.  
Depending on the call disconnect the Y, W or G wire from the zone 
terminal strip on the panel. The call from that zone will drop out 
when the thermostat wire is removed. Check the thermostat wiring 
for a mis-wiring or short that keeps the zone calling.   
 
If the thermostat wire is disconnected from the proper terminal on 
the zone and the zone LED remains lit, re-boot the panel to see if 
the call drops. If the call still stays on, turn power off to the panel for 
10 seconds and then turn back on. Once powered is restored and 
the thermostat is disconnected the call should drop from the zone. If 
not replace panel.   
 

Damper Motor Checkout Procedure 

In order to determine the operation of the damper motors, the panel 
motor plug can be checked to determine if power is being supplied 
from the panel. If there is power at the motor plug, the problem may 
be a broken wire or poor connection in the cord or the motor itself.   
 
To check the power to the motor from the damper plug on the panel, 
switch your meter to DC Volts. Note the wires on the plug and check 
across either Positive and Negative wires. Note that each plug has 
two positive leads and two negative leads. Both positive and both 
negative leads are wired together. The meter will read either Plus (+) 
or Minus (-) 12VDC depending if the damper is to be Open or 
Closed respectively.  
 
 

DAMPER CLOSED 

 

-12VDC

NOT USED

NOT USED

POSITIVE (+)

POSITIVE (+)

NEGATIVE (-)

MOTOR PLUG

VDC

-12VDC

NOT USED

NOT USED

POSITIVE (+)

POSITIVE (+)

NEGATIVE (-)

MOTOR PLUG

-12VDC

-12VDC

NOT USED

NOT USED

POSITIVE (+)

POSITIVE (+)

NEGATIVE (-)

MOTOR PLUG

VDC

 

 
When using multiple dampers on a single zone, please note to have 
no more than 6 dampers on a single zone. Adding dampers beyond 
the recommended number may cause all dampers to be slow to 
operate and may not fully cycle between open and closed.   
 
 

DAMPER OPEN 

+12VDC

NOT USED

NOT USED

POSITIVE (+)

POSITIVE (+)

NEGATIVE (-)

MOTOR PLUG

VDC

+12VDC

NOT USED

NOT USED

POSITIVE (+)

POSITIVE (+)

NEGATIVE (-)

MOTOR PLUG

+12VDC

+12VDC

NOT USED

NOT USED

POSITIVE (+)

POSITIVE (+)

NEGATIVE (-)

MOTOR PLUG

VDC

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 
 
 

 

5

Summary of Contents for PCMMP3

Page 1: ...Model PCMMP3 PCMMP3 ZONING SYSTEM 3 Zones For Plug In Damper Motors 1 ...

Page 2: ...ower transformer are wired When installing the PCMMP3 panel it is important to pick a central location where it is most convenient to bring all the wires Most often this is near the furnace or air handler and closest to power the HVAC unit controls and the zone dampers when typically located at or near the plenum The PCMMP3 case and cover are made of sturdy ABS plastic and can be mounted to any fl...

Page 3: ... Equipment Set Up The PCMMP3 is factory set for conventional fossil fuel oil or gas single stage heating and cooling The panel only needs to be configured when using with a conventional electric furnace or hydro air system in order to bring the fan on with a call for heat By using the FIH Fan On In Heat jumper located on the upper right corner of the board this allows the Fan to be activated with ...

Page 4: ...ting above its set point or cooling below its set point the PCMMP3 will drop both stages of heating or cooling The PCZPS must sense a 10nF fall for heating or rise for cooling before re activating the first stages of heating or cooling If two stage heating or cooling is being used the second stage timer will start again once the first stage is re activated The PCZPS requires 2 wires from the senso...

Page 5: ...e powered is restored and the thermostat is disconnected the call should drop from the zone If not replace panel Damper Motor Checkout Procedure In order to determine the operation of the damper motors the panel motor plug can be checked to determine if power is being supplied from the panel If there is power at the motor plug the problem may be a broken wire or poor connection in the cord or the ...

Page 6: ... BOOT Button Resets the microprocessor NO SENSOR Must be ON when not using Leaving Air Sensor and OFF when sensor is wired FIPG FIH TEST BOOT ON LOW LIMIT 24V TRANS C R C R T24 24V 40VA TRANSFORMER Y COMPRESSOR RELAY G FAN RELAY W HEAT RELAY R 24V TRANSFORMER C FURNACE CONTROLS OUTDOOR CONDENSING UNIT Y G W R EQUIPMENT G Y R W C ZONE THERMOSTAT G Y R W C 70 ZONE THERMOSTAT G Y R W C ZONE THERMOSTA...

Reviews: