background image

 

PCMMP3

 

ZONING SYSTEM

 

3 Zones 

Features

 

 

 

Table of Contents 

Installation ……………………………………….….…2-3 

Operation …………………………………………..…….3 

HVAC Equipment Set-Up…………..…………..……….3 

Checkout..………………………………………...………3 

Wiring ………………………………………………..…3-4 

Troubleshooting ………………………………….……4-5 

 

 

 

 

 
 
INSTALLATION 

The PCMMP3 Plug-In Damper Zoning System-3, Model MMP3, is a 
two (2) and three (3) zone control panel for single stage heating 
only, cooling only or heating and cooling. The PCMMP3 can control 
any single stage gas-oil-electric furnace, hydro-air heating and air 
conditioning. The PCMMP3 panel is the central control panel where 
all zone dampers, zone thermostats, HVAC Equipment and power 
transformer are wired.   
 
When installing the PCMMP3 panel it is important to pick a central 
location where it is most convenient to bring all the wires. Most often 
this is near the furnace or air handler and closest to power, the 
HVAC unit controls and the zone dampers when typically located at 
or near the plenum.   
 
The PCMMP3 case and cover are made of sturdy ABS plastic and 
can be mounted to any flat surface. It is recommended that the 
panel be mounted to a wall or return plenum and NOT on the 
furnace or plenum where it will be in contact with the high heating 
temperatures. The panel can be located in an attic space or in an 
enclosed cabinet of a rooftop unit, provided the panel enclosed and 
not in direct exposure to the elements.   
 

2

Summary of Contents for PCMMP3

Page 1: ...Model PCMMP3 PCMMP3 ZONING SYSTEM 3 Zones For Plug In Damper Motors 1 ...

Page 2: ...ower transformer are wired When installing the PCMMP3 panel it is important to pick a central location where it is most convenient to bring all the wires Most often this is near the furnace or air handler and closest to power the HVAC unit controls and the zone dampers when typically located at or near the plenum The PCMMP3 case and cover are made of sturdy ABS plastic and can be mounted to any fl...

Page 3: ... Equipment Set Up The PCMMP3 is factory set for conventional fossil fuel oil or gas single stage heating and cooling The panel only needs to be configured when using with a conventional electric furnace or hydro air system in order to bring the fan on with a call for heat By using the FIH Fan On In Heat jumper located on the upper right corner of the board this allows the Fan to be activated with ...

Page 4: ...ting above its set point or cooling below its set point the PCMMP3 will drop both stages of heating or cooling The PCZPS must sense a 10nF fall for heating or rise for cooling before re activating the first stages of heating or cooling If two stage heating or cooling is being used the second stage timer will start again once the first stage is re activated The PCZPS requires 2 wires from the senso...

Page 5: ...e powered is restored and the thermostat is disconnected the call should drop from the zone If not replace panel Damper Motor Checkout Procedure In order to determine the operation of the damper motors the panel motor plug can be checked to determine if power is being supplied from the panel If there is power at the motor plug the problem may be a broken wire or poor connection in the cord or the ...

Page 6: ... BOOT Button Resets the microprocessor NO SENSOR Must be ON when not using Leaving Air Sensor and OFF when sensor is wired FIPG FIH TEST BOOT ON LOW LIMIT 24V TRANS C R C R T24 24V 40VA TRANSFORMER Y COMPRESSOR RELAY G FAN RELAY W HEAT RELAY R 24V TRANSFORMER C FURNACE CONTROLS OUTDOOR CONDENSING UNIT Y G W R EQUIPMENT G Y R W C ZONE THERMOSTAT G Y R W C 70 ZONE THERMOSTAT G Y R W C ZONE THERMOSTA...

Reviews: