Page 21 Instruction manual Parker X-Flow FM-1407 Rev - 11/2021
Diagnostics (08)
The following sub-functions are supported:
Sub-function code
(dec)
Name
00
Return Query Data
10
Clear Counters and Diagnostics Register
11
Return Bus Message Count
12
Return Bus Communication Error Count
13
Return Bus Exception Error Count
14
Return Slave Message Count
15
Return Slave No Response Count
16
Return Slave NAK Count (always 0)
17
Return Slave Busy Count (always 0)
18
Return Bus Character Overrun Count
The maximum message size for the Return Query Data sub function is 100 bytes at 9600 baud
(200 bytes at 19200 baud and 400 bytes at 38400 baud). When this size is exceeded,
corrupted responses may be received.
Possible exception responses:
•
01, ILLEGAL FUNCTION, in case of not-supported sub-function
•
03, ILLEGAL DATA VALUE, in case of an incorrect value for the data field
Report Slave ID (17)
The Slave ID field in the response is a string with the same contents as FlowDDE parameter 1 (indent
version nr/serial nr). The Run Indicator Status field in this message will indicate ON when the
device is in normal operating mode (FB_NORMAL).
Possible exception responses:
•
04, SLAVE DEVICE FAILURE, in case of an internal error
3.5.5 Available parameters
Modbus® registers (in the data model) are numbered from 1 to 65536. In a Modbus® PDU (Protocol
Data Unit) these registers are addressed from 0 to 65535.
The following table lists the commonly used parameters.
MODBUS® REGISTERS
PARAMETER NAME
PARAMETER
TYPE
ACCESS
PDU ADDRESS
hex
REGISTER NUMBER
REMARK
Hex
Dec
Wink
Unsigned char
W
0x0000
0x0001
1
Value
14592
Init/reset
Unsigned char
RW
0x000A
0x000B
11
Valve output
Unsigned int
RW
0x001F
0x0020
32
0..32767
Measure
Unsigned int
R
0x0020
0x0021
33
Setpoint
Unsigned int
RW
0x0021
0x0022
34
Setpoint slope
Unsigned int
RW
0x0022
0x0023
35
Analog input
Unsigned int
R
0x0023
0x0024
36
Setp. control modes Unsigned char
RW
0x0024
0x0025
37
Sensor type
Unsigned char
RW
0x002E
0x002F
47
Capunit
Unsigned char
RW
0x002F
0x0030
48
Fluid number
Unsigned char
RW
0x0030
0x0031
49
Alarminfo
Unsigned char
R
0x0034
0x0035
53
Temperature
Unsigned int
R
0x0427
0x0428
1064
Identnumber
Unsigned char
RW
0x0E2C
0x0E2D
3629
ContrResp
Unsigned char
RW
0x0E45
0x0E46
3654
CycleTime
Unsigned char
R
0x0E4C
0x0E4D
3661
RespStable
Unsigned char
RW
0x0E51
0x0E52
3666
RespOpen0
Unsigned char
RW
0x0E52
0x0E53
3667
Calibration mode
Unsigned char
RW
0x0E61
0x0E62
3682
Monitor mode
Unsigned char
RW
0x0E62
0x0E63
3683
!