NOTE: If the control system is unable to successfully calibrate the pressure control regulator, an error
message will be displayed, and automatic startup will be aborted. An example of this error message
is shown below:
NOTE: There will be a system priming delay of approximately 25 second once boost pump has turned on
to when the HP Pump turns on.
4.
For Aqua Whisper DX system increase pressure to 950 PSI (65 BAR) by turning the regulator
valve.
NOTE: For Aquamatic & Aquamatic XL systems, after a further 60 seconds the system will activate the
automatic pressure regulator and start increasing system pressure until the desired product water
production rate has been achieved or until max pressure allowable (925 PSI - 65 BAR). If Max
pressure is achieved, you will get a warning message. This will most likely happen when you are in
low temperature, high salinity feed water, or when your membranes need cleaning or changing.
The Aquamatic and Aquamatic XL system will continue to operate in this high-pressure state and
will divert all potable water produced into the ships potable water storage tank.
NOTE: If the control system detects a dangerous condition, or a failure of a critical sensor during automatic
operation. The system will bring the Aquamatic, Aquamatic XL and AquaWhipser DX system to a
rapid stop, and display the detected failure in an alarm screen, as shown below: