
5
INLET CONDITION CHECKLIST
Review this checklist before operation of system. It is critical that all factors are carefully considered and met.
INLET SUPPLY
Inlet supply should be adequate to accommodate the maximum flow being delivered by the pump.
1. Open inlet valve and turn on supply to avoid starving the pump.
2. Avoid closed loop systems, especially with high temperature, ultra-high pressure or large volumes. Conditions
vary with regulating/unloader valve.
3. Low vapor pressure fluids, such as solvents, require positive heads to assure adequate inlet supply.
4. Higher viscosity fluids require that the pump be flooded to 60 PSI to assure adequate inlet supply.
5. Higher temperature fluids tend to vaporize and require positive heads to assure adequate inlet supply.
6. When using an inlet supply reservoir, size it to provide adequate supply of fluid to accommodate 6-10 minutes
retention time at the rated GPM (however, a combination of system factors can change this requirement).
Provide adequate baffling in the tank to eliminate air bubbles and turbulence. Install diffusers on all return lines to
the tank.
INLET LINE SIZE
Inlet line size should be adequate to avoid starving the pump. Pump suction should never operate in a vacuum.
1. Line size must be sufficient to allow free
flow of influent fluid at the pumping flow rate. Minimize the use of thick-
walled fittings, tees, 90-degree elbows, or valves in the inlet line of the pump to reduce the risk of flow restriction,
vacuum, and cavitation.
2. The inlet line MUST be a FLEXIBLE hose, NOT a rigid pipe, and REINFORCED ON SUCTION SYSTEMS to
avoid collapsing.
3. The simpler the inlet plumbing, the less the potential for problems. It is recommended to keep the length, number
of joints, and the number of inlet accessories to a minimum.
4. Use pipe sealant as appropriate to ensure airtight positive sealing pipe joints.
INLET PRESSURE
Inlet pressure should be between flooded (zero) to 60 PSI.
1. High RPM, high temperatures, low vapor pressures, or high viscosity reduces inlet pressure. The pump may
require a pressurized inlet to maintain adequate inlet supply.
CAUTION
DO NOT RUN PUMP DRY.
Summary of Contents for Pure Water Series
Page 2: ......
Page 3: ...THE PURE WATER SERIES 400 2000 GPD USER GUIDE REFERENCE MANUAL ...
Page 4: ......
Page 7: ......
Page 9: ......
Page 62: ...TROUBLESHOOTING Figure 8 0 Troubleshooting Flow Diagram T ...
Page 63: ...TROUBLESHOOTING Figure 8 0 Troubleshooting Flow Diagram CONTINUED T ...
Page 64: ...DRAWINGS AND DIAGRAMS 38 VMT v JUNE 2008 9 0 DRAWINGS AND DIAGRAMS ...
Page 65: ......
Page 66: ......
Page 67: ......
Page 75: ......
Page 76: ......
Page 77: ......
Page 78: ......
Page 79: ......
Page 80: ......
Page 81: ......
Page 82: ......
Page 83: ......
Page 84: ......
Page 85: ......
Page 86: ......
Page 87: ......
Page 88: ......
Page 89: ......
Page 90: ......
Page 91: ...PARTS REFERENCE 62 VMT v JUNE 2008 Drawing upgrade as of 4 1 2015 ...
Page 92: ......
Page 93: ......
Page 94: ......
Page 95: ......
Page 96: ......
Page 97: ......
Page 98: ......
Page 99: ......
Page 100: ......
Page 101: ......
Page 102: ......
Page 103: ......
Page 104: ...PARTS REFERENCE 39 VMT v JUNE 2008 10 0 PARTS REFERENCE ...
Page 105: ......
Page 106: ......
Page 107: ......
Page 108: ......
Page 109: ......
Page 110: ......
Page 111: ......
Page 112: ......
Page 113: ......
Page 114: ......
Page 115: ......
Page 116: ......
Page 117: ......
Page 118: ......
Page 119: ......
Page 120: ......
Page 121: ......
Page 122: ......
Page 123: ......
Page 124: ...MANUFACTURER S LITERATURE 92 VMT v JUNE 2008 Drawing upgrade as of 4 1 2015 ...
Page 135: ...MANUFACTURER S LITERATURE 40 VMT v JUNE 2008 11 0 MANUFACTURER S LITERATURE ...
Page 136: ......
Page 165: ...708 Series High Pressure Titanium Positive Displacement Pump 26 ...
Page 166: ...708 5 DRAWINGS ...