Installation of the individual drive PSD1-S
34 (109)
192-011006N8 2019-07
09.10.19 09:27
* The internal braking resistor is connected via bridge X63/1 and X63/2:
Device protection
By cyclically switching on and off the power voltage, the input current limitation
can be overloaded, which may cause damage to the device.
Wait at least one minute between two switching on processes!
Please note!
If neither a braking resistor nor a bridge are connected, the intermediate circuit
voltage is 0.
4.7.1.
Mains connection PSD1-S
Category
Specifications
PSD1-S
PSD1-S_1200
PSD1-S_1300
Mains voltage
3 phases 3* 230 VAC ±10%
30 ... 253 VAC / 50-60 Hz
or
Single Phase 230 VAC ±10%
30 ... 253 VAC / 50-60 Hz
Input Current
1AC230V: 6.8 Arms
3AC230V: 1.7 Arms
1AC230V: 11 Arms
3AC230V: 4.2 Arms
Maximum fuse per
device*
Single phase: 8 A
Three phases: 3 A
Fuse Class: gS (gRL), Time-delay
Single phase: 12 A
Three phases: 6 A
Fuse Class: gS (gRL), Time-delay
Earth leakage current
Current on the mains PE (see page 24) (>3,5 mA)
Supply networks
Possible supply networks (see page 24): TN
*
Circuit breakers for operation according to CE.
Circuit breakers for UL und CSA see Chapter UL (see page 18, see page 21).
Please observe the notes in chapter “
Operating conditions for CE-conform
operation
(see page 13)“.
4.7.2.
Braking operation PSD1-S
Category
Specifications
Controller type
PSD1-S_1200 (2 A)
PSD1-S_1300 (5 A)
Capacity/ storable
energy
760
µ
F / 15 Ws
1140
µ
F / 23 Ws
Minimum braking
resistance
51
Ω
51
Ω
Maximum current
7.84 A
7.84 A