![Parker P33 Integration Manual Download Page 27](http://html2.mh-extra.com/html/parker/p33/p33_integration-manual_4396739027.webp)
Parker Hannifin Corporation
Pneumatic Division Europe
www.parker.com/pde
25
Omron G9SP-N10S
Integration Guide
Omron G9SP-N10S
FRL-SIF-120
_EU
Parker Pneumatic
External Monitoring program for Omron G9SP-N10S
a) If Si0 = Si1 = 1 AND safety hardwire circuit in Active state AND no faults present THEN SET So0 = So1 = 1
when commanded
b) Sensor discrepancy error: Si0 <> Si1 (max. discrepancy time = 150 msec)
c) Loss of pressure error: So0 = So1 = 1 AND Si0 = Si1 = 0
followed by Si0 = 1 OR Si1 =1 AND So0 = So1 = 1
d) System pressure error: So0 = So1 = 1 AND Si0 = Si1 = 1 for x amount of time (where x is system pressurization
time dependent on volume) Default 3 secs.
e) IF sensor discrepancy error OR loss of pressure error OR system pressure error THEN reset So0 = So1 = 0
Errors must be reset only after maintenance acknowledgement
* Programs provided in this integration guide are for reference only. These programs have not been certified or tested
unless stated otherwise.