70 - PVD 3664_GB_NK-November 2016.Docx
Example of sizes for H07 RN-F cable :
Conditions of use:
Case of 3 conductors type H07 RN-F:
60°C maximum
Ambient temperature: 30°C
Cable runs on dedicated cables ways
Current limited to 80%*I
0
at low speed or at motor stall.
Example:
Io=100 Arms
Permanent current at standstill : 80 Arms
Max permanent current in the cable = 113 Arms
Cable section selection = 35mm² for a 3 cores in a cable tray at 30°C max.
You also have to respect the Drive commissioning manual and the cables current
densities or voltage specifications
3.7.2.
Conversion Awg/kcmil/mm²:
Awg
kcmil
mm²
500
253
400
203
350
177
300
152
250
127
0000 (4/0)
212
107
000 (3/0)
168
85
00 (2/0)
133
67.4
0 (1/0)
106
53.5
1
83.7
42.4
2
66.4
33.6
3
52.6
26.7
4
41.7
21.2
5
33.1
16.8
6
26.3
13.3
7
20.8
10.5
8
16.5
8.37
9
13.1
6.63
10
10.4
5.26
11
8.23
4.17
12
6.53
3.31
14
4.10
2.08
16
2.58
1.31
18
1.62
0.82
20
1.03
0.52
22
0.63
0.32
24
0.39
0.20
26
0.26
0.13
Summary of Contents for NK Series
Page 1: ...1 PVD 3664_GB_NK November 2016 Docx Servomotors NK Series Technical Manual PVD 3664_GB ...
Page 40: ...40 PVD 3664_GB_NK November 2016 Docx 3 3 Dimension drawings 3 3 1 NK1 ...
Page 41: ...41 PVD 3664_GB_NK November 2016 Docx 3 3 2 NK2 ...
Page 42: ...42 PVD 3664_GB_NK November 2016 Docx 3 3 3 NK3 ...
Page 43: ...43 PVD 3664_GB_NK November 2016 Docx 3 3 4 NK4 ...
Page 44: ...44 PVD 3664_GB_NK November 2016 Docx 3 3 5 NK6 ...
Page 45: ...45 PVD 3664_GB_NK November 2016 Docx 3 3 6 NK8 ...
Page 46: ...46 PVD 3664_GB_NK November 2016 Docx 3 3 1 NK3 W ...
Page 47: ...47 PVD 3664_GB_NK November 2016 Docx 3 3 2 NK4 W ...
Page 48: ...48 PVD 3664_GB_NK November 2016 Docx 3 3 3 NK6 W ...
Page 49: ...49 PVD 3664_GB_NK November 2016 Docx 3 3 4 NK8 W ...
Page 76: ...76 PVD 3664_GB_NK November 2016 Docx Resolver part number 220005P1003 ...