background image

Parker Hannifin Corporation  

Industrial Gas Filtration and Generation Division  
Haverhill, MA 

•  1-800-343-4048

 

Parker Zero Air Generators 

Models HPZA-3500, HPZA-7000, HPZA-18000, HPZA-30000

 

 

Bulletin TI-HPZA-3500H

 

 

     

 

 

Filter Cartridge 
Replacement

 

 
 
 
 
 
 
 
 
 

 

Catalyst Module 
Maintenance

 

 

 
 

The Grade DX and Grade BX prefilters integral to the Parker Zero Air Generator are located on the right 
side of the generator, behind the removable panel (see Figure 6). The filter cartridges inside the prefilter 
housings should be changed on an annual basis to maintain efficient operation of the system. The filter 
cartridges housed in the prefilters are removed by unscrewing the collar from the head of the filter 
assembly, lowering the bowl of the assembly, and removing the element retainer disc at the base of the 
cartridge. Insert the new filter cartridges (100-12-DX and 100-12-BX) and re-assemble in reverse order. 
(

Note: 

The filter housings are labeled for Grade DX and Grade BX filter cartridges. Please install 

replacement cartridges in the correct housing.)

 

The final membrane filter in the Parker Zero Air Generator is also easily accessible from the right side of 
the unit. The membrane filter should also be changed each year, or as needed to maintain flow and 
minimize pressure drop. The membrane filter cartridge is removed by unscrewing the filter bowl from 
the filter head and sliding the spent cartridge off the support core.  Replace the GS membrane cartridge 
(GS-050-05-95) and re-assemble.

 

The time required to service all three stages of filtration integral to the Parker Zero Air Generator is 
approximately 15 minutes.

 

 

 

To prevent electrical shock, disconnect the generator from the power supply prior to ser vicing the 
catalyst module.

 

 

Allow unit to cool for at least 2 hours before removing the cover to service the catalyst module.

 

The catalyst module in the Parker Zero Air Generator should be changed (when the 

“Check System” 

LED is illuminated or blinking) to maintain the hydrocarbon removal specification for the unit. Contact 
the local representative for ordering information and pricing for a replacement catalyst module.

 

The tools required to change the catalyst module  are a Phillips head screwdriver, an 11/32

” nut driver, 

and two 7/16” or adjustable wrenches.  The procedure for replacing the catalyst module is as follows (see 
Figure 6 for component locations):

 

Switch off the power to the unit, unplug from the power receptacle, close the (customer 
installed) inlet air valve, and allow the unit to cool (2 hours, minimum) and depressurize.

 

Remove the cover from the Zero Air Generator.

 

Using two wrenches (one as an anchor), disconnect the module inlet and outlet fittings at the 
elbow. 

Leave both elbows on the module 

(see Figure 6).

 

Remove the washer and kep nut (11/32

”) at the base of the module.

 

Remove the spent module from the Zero Air Generator and disconnect the electrical connector 
and the PCB connector (see Figure 6).

 

 

 

Figure 6 

– Maintenance Items

 

100-12-BX COALESCING 
 FILTER CARTRIDGE

 

100-12-DX COALESCING 
 FILTER CARTRIDGE

 

Summary of Contents for HPZA-3500

Page 1: ...e 1 are completely engineered systems which replace the use of inconvenient high pressure gas cylinders as a source of hydrocarbon free air The HPZA 30000 generators purify on site compressed air to a...

Page 2: ...rs are equipped with float drains which automatically open to empty any liquids from inside the filter housing The drains are connected to 1 4 O D plastic tubing which discharges to atmosphere onthe r...

Page 3: ...re taken into consideration Approximately 6 of space should be allowed along the top and sides of the generator to ensure proper ventilation Compressed Air The Parker Zero Air Generator requires a sou...

Page 4: ...ion only Piping Components The inlet and outlet ports for the Parker Zero Air Generator are 1 4 NPT female and located on right side of the unit Inlet tubing and fittings should be clean and rated for...

Page 5: ...stream from the generator Exposure of the generator to halogenated hydrocarbons will damage the catalyst module and void the warranty For additional information request the Analytical Gas Supplies cat...

Page 6: ...carbon content of less than 0 05 ppm Models HPZA 3500 HPZA 7000 and HPZA 18000 a flow control device must be installed downstream from the generator to prevent downstream demand in excess of the gener...

Page 7: ...Replace the GS membrane cartridge GS 050 05 95 and re assemble The time required to service all three stages of filtration integral to the Parker Zero Air Generator is approximately 15 minutes To prev...

Page 8: ...tor may burn out The fuses are located in the power receptacle on the left hand side of the generator Before servicing the fuses turn the generator off and disconnect the power cord from both the powe...

Page 9: ...generator is exceeded Overflow LED and yellow THC LEDs will illuminate An excessive pressure drop greater than 4 psig 0 3 bar may accompany an overflow situation If demand exceeds capacity install a f...

Page 10: ...arg 40 psig 125 psig 2 8 barg 8 6 barg 40 psig 125 psig 2 8 barg 8 6 barg Min Max ambient temperature 60 F 16 C 100 F 38 C 60 F 16 C 100 F 38 C 60 F 16 C 100 F 38 C 60 F 16 C 100 F 38 C Max relative h...

Page 11: ...calling for assistance WARRANTY NORTH AMERICA ONLY FOR INFORMATION CONTACT YOUR LOCAL REPRESENTATIVE Parker Hannifin guarantees to the original purchaser of this product that if the product fails or i...

Page 12: ...800 343 4048 Symbol Parker Hannifin Corporation Industrial Gas Filtration and Generation Division 242 Neck Road Haverhill MA 01835 www parker com labgas Description Caution Refer to accompanying docum...

Reviews: