Parker EME
Conditions of utilization
2.7.2.
Conditions of utilization for UL approval Compax3M
UL approval for Compax3M
Conform to UL:
in accordance with UL508C
Certified
E-File_No.: E235342
The UL approval is documented by a
“UL” logo on the device (type
specification plate).
Conditions of utilization
The devices are only to be installed in a degree of contamination 2 environment
(maximum).
The devices must be appropriately protected (e.g. by a switching cabinet).
Tightening torque of the field wiring terminals ( green Phoenix plugs)
Device
X43: Motor connector
X15: Temperature monitoring
C3M050-150
0.5Nm (4.43Lb.in)
0.22Nm (1.95Lb.in)
C3M300
1.2Nm (10.62Lb.in)
0.22Nm (1.95Lb.in)
Temperature rating of field installed conductors shall be at least 60°C. Use
copper lines only
Please use the cables described in the accessories chapter, they feature a
temperature rating of at least 60°C.
Maximum Surrounding Air Temperature: 40°C.
Control voltage supply (24VDC) only permissible with "class 2" power supply.
Compax3M may only be operated with a mains module of the PSUP series.
Motor Over Temperature sensing is not provided by the drive unless the external
temperature sensor is connected.
Caution!
Risk of electric shock.
Discharge time of the bus capacitor is 10 minutes.
The drive provides internal motor overload protection.
This must be set so that 200% of the motor nominal current are not exceeded.
Cable cross-sections
Mains input: corresponding to the recommended fuses.
Motor cable: corresponding to the Nominal output currents
Maximum cross-section limited by the terminals mm
2
/ AWG
Line cross-sections of the power connections (on the device bottoms)
Compax3 device:
Cross-section: Minimum... Maximum [with conductor sleeve]
M050, M100, M150
0.25 ... 4 mm
2
(AWG: 23 ... 11)
M300
0.5 ... 6 mm
2
(AWG: 20 ... 10)
192-
120148N13 2019-06
11