Introduction
Use of the devices in the industrial area (limit values class C3 in accordance
with EN 61800-3)
The following mains filters are available for independent utilization:
Device: PSU
Limit value
class
Reference: Axis system
with motor cable
Mains filter
Order No.:
P10
C3
< 6 x 10 m
NFI03/01
P10
C3
< 6 x 50 m
NFI03/02
P20
C3
< 6 x 50 m
NFI03/03
P30
C3
< 6 x 50 m
NFI03/03
Connection length: Connection between mains filter and device:
unshielded:
< 0.5 m
shielded
< 5 (fully shielded on ground - e.g. ground of control cabinet)
2.7.1.2
Conditions of utilization for cables / motor filter
Motor and Feedback
cable:
Operation of the devices only with motor and feedback cables whose plugs
contain a special full surface area screening.
<80m per axis (the cable must not be rolled up!)
The entire length of the motor cable per axis combination may not exceed 300m.
A motor output filter is required for motor cables >20 m:
ECM-0001-04 (max. 6.3 A nominal motor current)
ECM-0001-01 (max. 16 A nominal motor current)
ECM-000 1-02 (m ax. 30 A nom inal m otor current)
Shielding connection of
the motor cable
The cable must be fully-screened and connected to the device housing. Use the
cable clamps/shield connecting terminals furnished with the device.
The shield of the cable must also be connected with the motor housing. The fixing
(via plug or screw in the terminal box) depends on the motor type.
< 80m
Corresponding to the specifications of the terminal clamp with a temperature range
of up to 60°C.
Cable installation:
Signal lines and power lines should be installed as far apart as possible.
Signal lines should never pass close to excessive sources of interference
(motors, transformers, contactors etc.).
Do not place mains filter output cable parallel to the load cable.
2.7.1.3
Additional conditions of utilization
Motors:
Operation with standard motors.
Control:
Use only with aligned controller (to avoid control loop oscillation).
Grounding:
Connect the filter housing and the device to the cabinet frame, making sure that
the contact area is adequate and that the connection has low resistance and low
inductance.
Never mount the filter housing and the device on paint-coated surfaces!
Accessories:
Make sure to use only the accessories recommended by Parker.
Connect all cable shields at both ends, ensuring large contact areas!
This is restricted operation category product according to EN 61800-3. This product
can cause high-frequency disturbance in domestic areas. Users are asked to take
suitable action if this proves to be the case.
Compax3M motor
cable
Compax3M encoder
cable:
Cable
10
192-
120148N13 2019-06
Multi-axis devices