MSC4000 - MSC15000 USER GUIDE
A16 ACTIVE ALARMS
MODEM FAILURE
Press RESET to Clear
R1 COMPR #1
[ENABLED]
COMPR#2 ENABLED
COMPR#3 ENABLED
COMPR#4 DISABLED
R2 COMPR #1 ENABLED
COMPR#2
[ENABLED]
COMPR#3 ENABLED
COMPR#4 DISABLED
R3 COMPR #1 ENABLED
COMPR#2 ENABLED
COMPR#3
[ENABLED]
COMPR#4 DISABLED
R5
AUTO-SWITCH TIME:
24 Hrs
R4 COMPR #1 ENABLED
COMPR#2 ENABLED
COMPR#3 ENABLED
COMPR#4
[DISABLED]
ACTIVE ALARMS
No Active Alarms
Press RESET to EXIT
COMPRESSOR
MENU
Press SET to Select
A16 Drain Requires a manual reset.
Auto-Sequence “Time” can be selected between 1 & 72 hours.
NOTE:
When set to “TEST”, units will sequence STANDBY
COMPRESSOR every 3 minutes (also see the K10 Menu in
DISPLAY VALUES).
SELECT “ENABLE or DISABLE”