21
MSC4000 - MSC15000 USER GUIDE
M37 ALARM #13
W4: HIGH AIR-IN ºF
M40 ALARM #14
W5: HIGH AMBIENT/H
2
0
RELAY PAGER REMOTE
Yes N/A N/A
M43 ALARM #15
W5: HIGH AMBIENT/H
2
0
RELAY PAGER REMOTE
Yes N/A N/A
M46 ALARM #16
MODEM FAULT
RELAY PAGER REMOTE
Yes N/A N/A
H1 ENGLISH / METRIC
SELECT UNITS: (ENGLISH)
H2 METRIC PRESSURES:
BAR OR KP
H3 INLET PRESSURE
ACTUAL:
93 PSI
OFFSET
[0 psi]
FULLSCALE
200 PSI
H4 INLET PRESSURE
ACTUAL:
93 PSI
OFFSET
[0 psi]
FULLSCALE
200 PSI
H5 Outlet Pressure
Actual:
0 psi
Offset
[0 psi]
Fullscale
200 psi
H6 Outlet Pressure
Actual:
0 psi
Offset
0 psi
Fullscale
[200 psi]
H7 Discharge Pressure
Actual:
3 psi
Offset
0 psi
Fullscale
[600 psi]
H8 Discharge Pressure
Actual:
0 psi
Offset
0 psi
Fullscale
[600 psi]
CALIBRATION MENU
Each of the transducers in the system has their ranges set in the “H” series screens. It
is important that the value indicated in the screens match the maximum range of the transducer span. If while
servicing the dryer and a different ranged transducer is replacing a factory installed transducer, make certain a
corrected value for maximum range is entered in the appropriate screen.