Parker ADAPTOMODE A4AO Installation, Service And Parts Information Download Page 5

Refrigerating Specialties Division

5

Maintenance and Service 

(continued)

Electrical

The Refrigerating Specialties Division molded water resistance Class “B” 

solenoid  coil  is  designed  for  long  life  and  powerful  opening  force.  The 

standard  coil  housing  meets  NEMA  3R  and  4  requirements.  This  sealed 

construction can withstand direct contact with moisture and ice. The coil 

housing far exceeds the requirements of NEMA Standard ICS, 1-110.57 salt 

spray test for rust resistance.
By  definition,  Class  “B”  coil  construction  will  permit  coil  temperatures 

as measured by resistance method, as high as 130°C (266°F). Final coil 

temperatures are a function of both fluid and ambient temperatures. The 

higher  fluid  temperatures  require  lower  ambient  temperatures  so  the 

maximum  coil  temperature  is  not  exceeded.  Conversely,  low  fluid  tem-

peratures permit higher ambient temperatures.
The  molded  Class  “B”  coil  is  available  from  stock  with  most  standard 

voltages. However, coils are available for other voltages and frequencies, 

as well as for direct current. Coils are also available as transformer type 

with a 6 volt secondary winding for use with the Refrigerating Specialties 

Division  Pilot  Light  Assembly  (see  current  copy  of  Bulletin  60-10,  “Pilot 

Light Assembly and Solenoid Transformer Coil”). The solenoid coil must 

be connected to electrical lines with volts and Hertz same as stamped on 

coil. The supply circuits must be properly sized to give adequate voltage 

at the coil leads even when other electrical equipment is operating. The 

coil is designed to operate with line voltage from 85% to 110% of rated 

coil voltage. Operating with a line voltage above or below these limits may 

result in coil burnout. Also, operating with line voltage below the limit will 

definitely result in lowering the valve opening pressure differential. Power 

consumption during normal operation will be 33 Watts or less.
Inrush and running current is listed below:
 

 

 

Inrush  Running 

Fuse 

 

Standard Coil 

 

Current  Current 

Size 

 

Volts/Hertz 

 

(Amps) 

(Amps) 

(Amps)

120/60 (Blue leads) 

 

1.86 

0.46 

208/60 (Blue & Red leads) 

 

0.63 

0.26 

240/60 (Red leads) 

 

0.60 

0.23 

440/60 (Yellow & Red leads) 

 

0.39 

0.13 

115/50 (Yellow & Blue leads) 

 

1.22 

0.21 

230/50 (Yellow leads) 

 

0.65 

0.26 

Other 

 

 

       (Contact Factory) 

On transformer coil the 6 volt leads are always black.  

 

 

SERVICE POINTERS (Check General Procedure)

 

SYMPTOM 

PROBABLE REASON 

CORRECTION 

  Regulator does not 

  shut off flow. 

Diaphragm or seat dirty, damaged or frozen.  

Clean or replace. Clean strainer. 

   

Diaphragm follower stuck or damaged. 

Clean or replace. Install follower carefully. 

   

Piston jammed with excess dirt. 

Remove and polish piston and bore with crocus cloth. Clean valve and strainer.

   

Modulating plug leaking due to excess dirt 

Clean or replace. If used on liquid, check for erosion due to excessive 

   

or damage. 

flash gas. Reduce flash gas by subcooling or by reducing pressure 

   

 

drop across valve by providing restriction at valve outlet. 

   

Diaphragm ruptured or badly deformed. 

Replace. If Range “D” make sure has 2 diaphragms. 

   

A4AOS/A4AOSE Modular Solenoid Pilot 

   

Seat leaking. 

Check seat and needle. Replace as needed. 

   

Diaphragm and seat eroded due to flash gas. 

Replace. Reduce flash gas by subcooling or by reducing pressure 

   

 

drop across regulator by providing restriction at valve outlet. 

   

Modular Solenoid Pilot not closing. 

Check power at leads, make sure coil is de-energized. 

  Regulator does not 

Pressure Regulator Diaphragm 

Replace. If Range D make sure has 2 

  open. 

ruptured or badly deformed. 

diaphragms. 

   

Diaphragm follower stuck, damaged 

Clean or replace. 

   

or frozen. 

Install follower carefully. 

   

A4AOS/A4AOSE Modular Solenoid 

Pressure drop across valve too high; over 21 bar (300 psig). Lower 

   

Pilot not opening. 

pressure drop. Improper power supply. Correct. Replace solenoid coil. 

   

Piston worn, too much clearance. 

Replace piston. Check for reason. If used on liquid, check for flash gas. 

   

Piston jammed with excess dirt. 

Remove and polish piston and bore with crocus cloth. 

   

 

Clean valve and strainer. 

  Regulator Operation 

Diaphragm or seat dirty 

  erratic. 

or damaged. 

Clean or replace. Clean strainer. 

   

Diaphragm follower has dirt on the outside 

   

diameter or outside diameter is damaged. 

Clean or replace. 

   

Other system components, line controllers, 

   

thermostats, etc., erratic. 

Adjust, repair or replace. 

   

Regulator too far oversized. 

Check load. Replace with smaller regulator or investigate use of 

   

 

reduced capacity plug. 

  Pressure drop across 

Inlet or outlet restricted. 

Check for restriction.  

 

  regulator too high. 

 

Clean strainer.

   

Regulator too small. 

Open manually to be sure valve is full open. 

   

 

Replace with proper size regulator. 

   

Large amount of flash gas in liquid line. 

Reduce flash gas by subcooling. Reduce line restriction by increasing line 

   

 

size, particularly at the regulator outlet. Replace with larger regulator. 

   

High pressure drop causes high rate of 

   

expansion gas at regulator outlet. 

Increase pipe size at the outlet of the regulator. 

   

Regulator does not open all the way. 

Check piston for wear. Replace, if needed. 

Summary of Contents for ADAPTOMODE A4AO

Page 1: ...g and will gradually open when pressure begins to fall below the setting The regulator cannot maintain set for pressure if uncontrolled branch pipe lines feed into the main pipeline downstream of the...

Page 2: ...odudapter Fig 2 item 28A is used only with the A4AOS The Pilot Solenoid is mounted on Pad 1 of the Modudapter along with Moduplate item 52 mounted on Pad 2 with S showing to the outside of the regulat...

Page 3: ...s are cold since moisture can condense on parts and cause rapid rusting When replacing gaskets they should be oiled very lightly with refrigerant oil before assembly Install bottom cap assembly rst an...

Page 4: ...ead Safety Bulletin RSB Dirt in the system is the greatest single cause of regulator malfunction All screens or lters must be cleaned or replaced when they become dirty At start up it is especially im...

Page 5: ...or does not shut off ow Diaphragm or seat dirty damaged or frozen Clean or replace Clean strainer Diaphragm follower stuck or damaged Clean or replace Install follower carefully Piston jammed with exc...

Page 6: ...1 1 200771 1 19 Gasket Only Avail with Kit 1 Only Avail with Kit 1 22 Nut Retainer Only Avail with Kit 1 Only Avail with Kit 1 23 Spring Only Avail with Kit 1 Only Avail with Kit 1 24 Plug Pilot Only...

Page 7: ...Only Avail with Kit 1 Only Avail with Kit 1 Only Avail with Kit 1 22 Only Avail with Kit 1 Only Avail with Kit 1 Only Avail with Kit 1 Only Avail with Kit 1 Only Avail with Kit 1 Only Avail with Kit...

Page 8: ...Cap Kit 202110 1 202110 1 33 38 40 44 Full Cap Bottom Assembly Kit 202010 1 202011 1 33 38 40 44 50 Cap Bottom Assembly Kit 202347 1 1 33 38 40 44 17 Cap Bottom Assembly Kit 202346 1 1 3 6 12 19 Full...

Page 9: ...y Avail with Kit 1 Only Avail with Kit 1 Only Avail with Kit 1 Only Avail with Kit 1 43 44 202110 1 202110 1 202110 1 202110 1 202110 1 202110 1 33 38 40 44 202012 1 202013 1 202014 1 202015 1 202016...

Page 10: ...4 4 Fig 4 Item Description Qty Kit Number 55 Screw 1 Only Avail with Kit 58 Coil Assemly 1 See Page 8 67 O Ring 1 Only Avail with Kit 68 Knob 1 Only Avail with Kit 67 68 Knob Kit 1 205047 69 Lens 1 On...

Page 11: ...18 6 525 20 7 538 21 2 657 25 9 710 28 4 B 148 5 8 162 6 3 177 6 9 181 7 1 273 10 7 292 11 5 C 177 6 7 216 8 5 264 10 4 264 10 4 324 12 7 352 14 6 D 1 2 229 9 0 1 1 4 269 10 6 FPT FOR 3 4 229 9 0 1 1...

Page 12: ...certain precautions be taken to avoid damage which could result from liquid expansion Temperature increase in a piping section full of solid liquid will cause high pressure due to the expanding liquid...

Reviews: