Function
Code
Function Definition
Setting Range
Mfr’s Value Change
FA01
PID reference signal
source
0: FA04
1: AI1
2: AI2
0
X
FA02
PID feedback signal
source
1: AI1
2: AI2
0
√
FA03
Max limit of PID output
(%)
FA04-100.0
10.00
√
FA04
PID Digital reference (%) FA05-FA03
50.0
√
FA05
Min limit of PID output
(%)
0.0-FA04
0.0
√
FA06
PID polarity
0: Positive feedback
1: Negative feedback
1
X
FA07
Sleep function
selection
0: Enabled 1: Disabled
0
X
FA09
PID Min output
frequency (Hz)
Max (F112, 0.1)-F111
5.00
√
FA10
Sleep delay time (s)
0-500.0
15.0
√
FA11
Wake delay time (s)
0.0-3000
3.0
√
FA18
Whether PID target is
changed
0: Disabled 1: Enabled
1
X
FA19
Proportion Gain P
0.00~10.00
0.3
√
FA20
Integration time I (s)
0.0~100.0S
0.3
√
FA21
Differential time D (s)
0.00~10.00
0.0
√
FA22
PID sampling period (s) 0.1-10.0s
0.1
√
FA29
PID dead time (%)
0.0-10.0
2.0
√
FA58
Fire pressure target
value (%)
0.0-100.0
80.0
√
FA59
Emergency fire mode
0: Disabled
1: Emergency fire mode
1
2: Emergency fire mode
2
0
√
FA60
Emergency fire mode
frequency
F112-F111
50.0
√
FA61
Reserved
FA62
When emergency
fire control terminal
transitions false
0: Inverter cannot be
stopped manually
1: Inverter can be
stopped manually
0
X
FA63-
FA80
Reserved
10-19
Parameter List and Default Settings
Summary of Contents for AC10 series
Page 13: ...Dimensions 2 8 This page intentionally left blank...
Page 15: ...Connections 2 10...
Page 19: ...Panel Display IP20 Units 3 4 Items and Remarks Displayed on the Panel...
Page 23: ...Menu Organization IP66 Units 3 8 Items and Remarks Displayed on the Panel...
Page 33: ...The Default Applications 8 2 Application 1 Basic Speed Control...
Page 34: ...8 3 The Default Applications Application 2 Auto Manual Control...
Page 35: ...The Default Applications 8 4 Application 3 Preset Speeds...
Page 36: ...8 5 The Default Applications Application 4 Raise Lower Trim...
Page 37: ...The Default Applications 8 6 Application 5 PID...