Function
Code
Function Definition
Setting Range
Mfr’s Value Change
F740
Reserved
F741
Analog Disconnected
Protection
0: Invalid
1: Stop and AErr
displays.
2: Stop and AErr is not
displayed.
3: Inverter runs at the
min frequency.
4: Reserved.
0
√
F742
Threshold of Analog
Disconnected
Protection (%)
1-100
50
o
F745
Threshold of Pre-alarm
Overheat (%)
0~100
80
o*
F747
Carrier Frequency
Auto-adjusting
0: Invalid 1: Valid
1
√
F754
Zero-current Threshold
(%)
0-200
5
X
F755
Duration time of zero-
current
0-60
0.5
√
Function
Code
Function Definition
Setting Range
Mfr’s Value Change
F800
Motor’s Parameters
Selection
Setting range:
0: Invalid;
1: Rotating tuning.;
2: Stationary tuning
0
X
F801
Rated Motor Power
0.2-1000kW
oX
F802
Rated Motor Voltage
1-440V
oX
F803
Rated Motor Current
0.1-6500A
oX
F804
Number of Motor Poles 2-100
4
oX
F805
Base Motor RPM
1-30000
oX
F806
Stator Resistance Ω
0.001-65.53Ω (22kw
and below)
0.1~6553mΩ (above
22kw)
Subject
to inverter
model
oX
Parameter List and Default Settings
10-16
Summary of Contents for AC10 series
Page 13: ...Dimensions 2 8 This page intentionally left blank...
Page 15: ...Connections 2 10...
Page 19: ...Panel Display IP20 Units 3 4 Items and Remarks Displayed on the Panel...
Page 23: ...Menu Organization IP66 Units 3 8 Items and Remarks Displayed on the Panel...
Page 33: ...The Default Applications 8 2 Application 1 Basic Speed Control...
Page 34: ...8 3 The Default Applications Application 2 Auto Manual Control...
Page 35: ...The Default Applications 8 4 Application 3 Preset Speeds...
Page 36: ...8 5 The Default Applications Application 4 Raise Lower Trim...
Page 37: ...The Default Applications 8 6 Application 5 PID...