background image

AC10 series

Quick-Start Guide
IP20 0.25 - 250 HP (0.2 - 180 kW)
IP66 0.5 - 125 HP (0.4 - 90 kW)

AC10 Expanded Quick-Start Guide 

HA474130U002 Issue 1

Summary of Contents for AC10 series

Page 1: ...AC10 series Quick Start Guide IP20 0 25 250 HP 0 2 180 kW IP66 0 5 125 HP 0 4 90 kW AC10 Expanded Quick Start Guide HA474130U002 Issue 1...

Page 2: ...utors provide component or system options based upon data or specifications provided by the user the user is responsible for determining that such data and specifications are suitable and sufficient f...

Page 3: ...d IP20 3 1 Remote Keypad 3 1 Menu Structure 3 2 Parameter Setting 3 2 Function Codes Fault Codes 3 3 The Keypad IP66 3 5 Menu Structure 3 6 Parameter Setting 3 6 Basic Speed Control Startup 4 1 Troubl...

Page 4: ...y 1 This equipment can endanger life by exposure to rotating machinery and high voltages 2 The equipment must be permanently earthed due to the high earth leakage current and the drive motor must be c...

Page 5: ...ostatic discharge ESD sensitive parts Observe static control precautions when handling installing and servicing this product This is a product of the restricted sales distribution class according to I...

Page 6: ...cted rotation of the motor will not result in bodily harm or injury This document expects that the drive is already installed in its intended location and that all relevant installation procedures hav...

Page 7: ...C10 Model This basic diagram shows the location of main drive components that will be referred to in this manual The diagram is representative of the product but some sizes may appear different than t...

Page 8: ...ut voltage range and rated frequency 3Ph 3 phase output 6 5A 2 2kW rated output current and power 1 Product Family 10 AC10 VFD IP20 2 Industry G General Purpose 3 Voltage 1 230V Single Phase 3 230V Th...

Page 9: ...0100 3 HP 2 2 kW 480V Supply 1 0020 1 HP 0 75 kW 1 0040 2 HP 1 5 kW 1 0065 3 HP 2 2 kW 1 0090 5 HP 4 0 kW 2 0120 7 5 HP 5 5 kW 2 0170 10 HP 7 5 kW 3 0230 15 HP 11 kW 3 0320 20 HP 15 kW 4 0380 25 HP 1...

Page 10: ...xL Mounting Bolt 1 10G X1 XXXX XX 80 135 138 153 2 76 1 25 70 128 M4 2 10G X2 XXXX XX 106 150 180 195 3 88 1 76 94 170 M4 3 10G 43 XXXX XX 138 152 235 250 6 53 2 96 126 225 M5 4 10G 44 XXXX XX 156 170...

Page 11: ...imension AxBxH H1 mm Weight lb kg Mounting Size WxL Mounting Bolt 6 10G 46 XXXX XX 265 x 235 x 435 37 48 17 235x412 M6 7 10G 47 XXXX XX 315 x 234 x 480 55 12 25 274x465 M6 8 10G 48 XXXX XX 360 x 265 x...

Page 12: ...xL Mounting Bolt 1 16G X1 XXXX XX 200 198 412 17 6 8 0 171 398 M5 2 16G X2 XXXX XX 242 198 418 22 1 10 0 215 402 M6 3 16G X3 XXXX XX 242 228 471 28 7 13 0 210 454 M8 4 16G X4 XXXX XX 242x323 5x650 61...

Page 13: ...Dimensions 2 8 This page intentionally left blank...

Page 14: ...n Output 24 VDC Modbus Communications IP66 drives have 6 digital inputs Refer to appendix for fuse sizing Braking Resistor Optional 2 9 Connections Terminal Tightening Torques This illustration is for...

Page 15: ...Connections 2 10...

Page 16: ...icating section and keypad operating section The remote mounted keypad can be ordered as 1001 00 00 This includes the keypad cable and mounting brackets Part Number A B C D H Opening 1001 00 00 124mm...

Page 17: ...the user can modify to effect different modes of operation The user should be aware that if they set password valid F107 1 the password must be entered first Parameter Setting Menu Structure Menu and...

Page 18: ...play function code If user presses or key the function code will circularly keep increasing or decreasing by degrees within the group if user presses the O key again the function code will change circ...

Page 19: ...Panel Display IP20 Units 3 4 Items and Remarks Displayed on the Panel...

Page 20: ...3 5 Keypad IP66 Units O M E E I O The panel covers three sections data display section status indicating section and keypad operating section Local Keypad IP66 Units...

Page 21: ...invalid before delivery and user could set corresponding parameters without entering password Keys Names Remarks Menu To call function code and switch over display sEt To call and save data Up To inc...

Page 22: ...keypad controller will display function code If user presses or key the function code will circularly keep increasing or decreasing by degrees within the group if user presses the key again the functi...

Page 23: ...Menu Organization IP66 Units 3 8 Items and Remarks Displayed on the Panel...

Page 24: ...t ton 1 time and the DGT LED will go out Pressing the u now allows the user to change Function Code groups and move from the F100 group to F200 through FC40 to access the group needed Once the approp...

Page 25: ...repeat steps 11 and 12 to verify correct rotation 14 Perform motor autotuning by setting Function code F800 If the motor is uncoupled from the load perform a rotating autotune by setting F800 to 1 Th...

Page 26: ...1 Rated Motor Power 0 2 1000kW oX F802 Rated Motor Voltage 1 440V oX F803 Rated Motor Current 0 1 6500A oX F804 Number of Motor Poles 2 100 4 oX F805 Base Motor RPM 1 30000 oX F800 Motor s Parameters...

Page 27: ...oltage is normal Check if parameter setting is correct O H Heatsink Overheat Environment temperature too high Poor ventilation Fan damaged Carrier wave frequency or compensation curve is too high Impr...

Page 28: ...g U V W wiring correct Parameters setting correct Correct wiring Set the parameters correctly Motor Turning but Speed Change not Possible Wiring correct for lines with given frequency Correct setting...

Page 29: ...e Install device in pollution degree 2 environment Or equivalent f Suitable for use on a circuit capable of delivering not more than 5 000 rms symmetrical amperes 480 240 volts maximum when protected...

Page 30: ...X 0 2 94 1 1 0 8 0 6 2 5 120 10 5 0 1 145 JJS 6 6 10G 41 0010 XX 0 37 94 1 5 1 2 1 5 10G 41 0015 XX 0 55 94 2 1 1 8 1 5 5 5 10G 42 0020 XX 0 75 94 3 2 1 2 6 5 JJS 15 15 10G 42 0030 XX 1 1 94 4 3 2 3 1...

Page 31: ...10 21 5 3 ph 460V 16G 41 0020 XX 0 75 94 3 2 1 2 7 120 10 5 0 1 145 JJS 15 15 16G 41 0040 XX 1 5 94 5 4 2 4 11 0 15 95 16G 41 0065 XX 2 2 94 7 5 7 0 6 5 15 16G 42 0090 XX 4 94 11 9 2 9 21 100 15 7 5...

Page 32: ...manual or auto set point Application 3 supplies speed control using preset speeds Application 4 supplies speed control using terminal Application 5 supplies speed control using PID Control wiring of a...

Page 33: ...The Default Applications 8 2 Application 1 Basic Speed Control...

Page 34: ...8 3 The Default Applications Application 2 Auto Manual Control...

Page 35: ...The Default Applications 8 4 Application 3 Preset Speeds...

Page 36: ...8 5 The Default Applications Application 4 Raise Lower Trim...

Page 37: ...The Default Applications 8 6 Application 5 PID...

Page 38: ...AC10 over Modbus Parker Drive Basic enables users to import modify and export drive parameters as well as providing a convenient means of starting stopping and monitoring the operation of the drive To...

Page 39: ...and is connected to the drive via a 1 5 meter cable that is provided with the option Remote Mounting Keypad Part Number 1001 00 00 Cloning Module AC10 drives may be cloned using the Parker cloning mod...

Page 40: ...2 X F107 Password Protection 0 Disabled 1 Enabled 0 F108 User s Password 0 9999 8 F109 Starting Frequency Hz 0 0 10 00Hz 0 0 F110 Holding Time of Starting Frequency S 0 0 999 9 0 0 F111 Max Frequency...

Page 41: ...Frequency B 0 00 590 0 Hz 0 00 F130 Skip Width B 2 50 Hz 0 00 F131 Running Display Items 0 Output frequency function code 1 Output RPM 2 Output current 4 Output voltage 8 DC Bus voltage 16 PID feedba...

Page 42: ...for settings N A N A X F153 Carrier frequency setting Subject to inverter model Subject to inverter model X F154 Automatic voltage rectification Setting range 0 Disabled 1 Enabled 2 Disabled during de...

Page 43: ...Keypad 0 X F203 Main frequency source X 0 Digital setting memory 1 External analog AI1 2 External analog AI2 3 Reserved 4 Stage speed control 5 No memory by digital setting 6 Reserved 7 Reserved 8 Re...

Page 44: ...peration mode 0 No function 1 Two line operation mode 1 2 Two line operation mode 2 3 three line operation mode 1 4 three line operation mode 2 5 start stop controlled by direction pulse 0 X F209 Moto...

Page 45: ...3000 0 60 0 F216 Auto start restart attempts 0 5 0 F217 Fault reset delay 0 0 10 0 3 0 F218 Reserved F219 Write EEPROM by Modbus 1 Disabled 0 Enabled 1 F220 Frequency memory after power down 0 Disabl...

Page 46: ...t manual for additional settings 1 F301 DO1 output 14 F302 DO2 output 5 F303 F306 Reserved F307 Target frequency 1 F112 F111 10 00 F308 Target frequency 2 F112 F111 50 00 F309 Target frequency width 0...

Page 47: ...witchover 1 19 58 refer to product manual for additional settings 11 F317 DI2 terminal function setting 9 F318 DI3 terminal function setting 15 F319 DI4 terminal function setting 16 F320 DI5 terminal...

Page 48: ...t true 1 Output false 0 X F336 DO1 output simulation 0 X F338 AO1 output simulation Setting range 0 4095 0 X F339 AO2 output simulation Setting range 0 4095 0 X F340 Selection of terminal negative log...

Page 49: ...ower limit of AI2 channel input 0 00 F408 0 01 F407 Corresponding setting for lower limit of AI2 input 0 F409 1 00 F408 Upper limit of AI2 channel input F406 10 00 10 00 F409 Corresponding setting for...

Page 50: ...ut signal selecting 0 Running frequency 1 Output current 2 Output voltage 3 Analog AI1 4 Analog AI2 6 Output torque 7 Given by PC PLC 8 Target frequency F432 AO2 analog output signal selecting F433 Co...

Page 51: ...g stopping 3 Braking during starting and stopping 0 X F601 Initial Frequency for DC Braking 0 20 50 00 1 00 F602 DC Braking level before Starting V A 0 100 10 F603 DC Braking level During Stop V A 0 1...

Page 52: ...ction memory 3 Flycatching from max freq and direction memory 0 X F615 Flycatching Rate 1 100 20 X F613 F621 Reserved F619 Flycatching fault Time out S 0 3000 60 F620 F621 Reserved F622 Dynamic Brakin...

Page 53: ...0 X F706 Inverter Overloading Setpoint 120 190 150 X F707 Motor Overloading Setpoint 20 100 100 X F708 Trip 1 Type Newest Setting range 2 Over current OC 3 Over voltage OE 4 Input phase loss PF1 5 Inv...

Page 54: ...Protection Faults D F722 Number of Overheat Protection Faults D F723 Number of Overload Protection Faults D F724 Input Phase Loss 0 Disabled 1 Enabled 1 oX F725 Reserved F726 Overheat 0 Disabled 1 En...

Page 55: ...valid 1 Valid 1 F754 Zero current Threshold 0 200 5 X F755 Duration time of zero current 0 60 0 5 Function Code Function Definition Setting Range Mfr s Value Change F800 Motor s Parameters Selection S...

Page 56: ...0 30 F813 Rotary Speed Loop KP1 0 01 20 00 22 kw and below 1 100 above 22 kw Subject to inverter model o F814 Rotary Speed Loop KI1 0 01 2 00 22 kw and below 0 01 10 00 above 22 kw Subject to inverter...

Page 57: ...n current compensation without load 0 0 50 0 0 0 X F878 PMSM cut off point of injection current compensation without load 0 0 50 0 10 0 X Function Code Function Definition Setting Range Mfr s Value Ch...

Page 58: ...500 0 15 0 FA11 Wake delay time s 0 0 3000 3 0 FA18 Whether PID target is changed 0 Disabled 1 Enabled 1 X FA19 Proportion Gain P 0 00 10 00 0 3 FA20 Integration time I s 0 0 100 0S 0 3 FA21 Differen...

Page 59: ...de can only be modified in stop state indicates that function code can be modified both in stop and run state D indicates that function code can only be checked in stop or run state but cannot be modi...

Page 60: ...parker greece parker com HK Hong Kong Tel 852 2428 8008 HU Hungary Budapest Tel 36 1 220 4155 parker hungary parker com IE Ireland Dublin Tel 353 0 1 466 6370 parker ireland parker com IN India Mumbai...