Installing the Converter
3-2
512C Series Converter
Mounting
the
Converter
Before connecting AC supplies to this equipment:
•
Ensure good airflow over the heatsink. Maintain clearance of 75mm above and below
controller. For safety maintain a clearance of 20mm at the sides of the controller.
•
Operating temperature range does not exceed 0 to +40øC.
•
Controller is used in a Pollution Degree 2 environment.
•
Avoid vibration.
Filter Installation
L1 L2
PE PE
LINE
LOAD
4 Holes M6 Insert
4 Holes M6 Clearance
230mm Leads
M5 Ring Lugs
A
B
C
D
L
W
E
H
PE
L1
L2
Black
Red
Green
/Yellow
Product Filter
Watt
Loss
Overall Dimensions
Fixing
Centres
Product
Fixing
Terminal
L W H E A B C D
512C/04 CO389113 18W 264 165 45 240 253 120 210 148 4mm2
512C/08 CO389113 18W 264 165 45 240 253 120 210 148 4mm2
512C/16 CO389113 18W 264 165 45 240 253 120 210 148 4mm2
512C/32 CO389114 36W 264 165 70 240 253 120 210 148 6mm2
Table 3.2 Filter Installation Information