  506/507/508 

 

 Product Manual 
 

HA389427  Issue 10

 

   

 

 

WARRANTY 

Parker SSD Drives warrants the goods against defects in design, materials and workmanship for the period of 12 

months from the date of delivery on the terms detailed in Parker SSD Drives Standard Conditions of Sale IA058393C.

 

Parker SSD Drives reserves the right to change the content and product specification without notice.

 

WWW.SDS.LTD.UK | 0117 9381800 

Summary of Contents for 506 Series

Page 1: ...acy of this document it may be necessary without notice to make amendments or correct omissions Parker SSD Drives cannot accept responsibility for damage injury or expenses resulting therefrom 506 507 508 Product Manual HA389427 Issue 10 WARRANTY Parker SSD Drives warrants the goods against defects in design materials and workmanship for the period of 12 months from the date of delivery on the ter...

Page 2: ...del Number see product label Where installed for your own information Unit used as a refer to Certification for the Inverter R Component R Relevant Apparatus Unit fitted R Wall mounted R Enclosure Application Area The equipment described is intended for industrial motor speed control utilising AC induction or AC synchronous machines Personnel Installation operation and maintenance of the equipment...

Page 3: ...re may still be dangerous voltages present at power terminals motor output supply input phases DC bus and the brake where fitted when the motor is at standstill or is stopped 5 For measurements use only a meter to IEC 61010 CAT III or higher Always begin using the highest range CAT I and CAT II meters must not be used on this product 6 Allow at least 5 minutes for the drive s capacitors to dischar...

Page 4: ...is rated for the highest system voltage Thermal sensors contained within the motor must have at least basic insulation All exposed metalwork in the Inverter is protected by basic insulation and bonded to a safety earth RCDs are not recommended for use with this product but where their use is mandatory only Type B RCDs should be used EMC In a domestic environment this product may cause radio interf...

Page 5: ...y not operate as intended In particular Stored energy might not discharge to safe levels as quickly as suggested and can still be present even though the drive appears to be switched off The motor s direction of rotation might not be controlled The motor speed might not be controlled The motor might be energised A drive is a component within a drive system that may influence its operation or effec...

Page 6: ...er 4 INSTALLING THE 506 507 508 Installation 4 1 Speed Control 4 1 Current Control 4 1 Wire Sizes 4 2 Requirements for UL Compliance 4 3 Motor Overload Protection 4 3 Short Circuit Protection Requirements 4 3 Short Circuit Rating 4 3 Operating Ambient Temperature 4 3 Field Wiring Temperature Rating 4 3 Field Wiring Terminal Markings 4 3 Power Wiring Terminals 4 3 Block Diagram 4 4 Terminal Tighten...

Page 7: ...the Unit to Parker SSD Drives 5 1 Chapter 6 CERTIFICATION FOR THE 506 507 508 Certificates 6 2 Chapter 7 TECHNICAL SPECIFICATION Input Supply 7 1 Speed Control 7 1 Current Torque Control 7 1 Adjustment Range 7 2 Environmental Requirements 7 2 EMC Technical Ratings 7 3 Immunity 7 3 Emissions 7 3 Electrical Ratings 7 4 Output Ratings with typical armature voltage Va 80 90V 160 180V 7 4 Adjustment Ra...

Page 8: ...Contents Contents Page ...

Page 9: ... the feedback signal A current loop within the speed feedback path ensures that safe current levels are always provided to the armature of the motor up to the level set by the maximum current potentiometer Imax This adjustment is linear and switchable to a lower range of half the controller current If the controlled motor is stalled e g due to either a faulty field circuit or an excessive load the...

Page 10: ...1 2 Product Overview 506 507 508 HA389427 WWW SDS LTD UK 0117 9381800 ...

Page 11: ...knob Switch Rated for input supply voltage Note Safety Components provide Isolation for the User These components should be selected to provide a double insulated or reinforced isolation boards for the user suitable for the input supply voltage used The product is designed for use in a pollution degree 2 environment overvoltage category III enclosure mounted Refer to EN61010 IEC664 or EN50178 for ...

Page 12: ...2 2 Overview of the 506 507 508 506 507 508 HA389427 ...

Page 13: ...o 10V to Run in Current Input Impedance 20k Ohm 4 Speed Setpoint Analogue Input 0v to 10V 0 to 100 Speed Input Impedance 66k Ohm 5 10V Reference Analogue Output 10V Reference for Speed and Current Setpoints Load 2mA 6 Current Limit Analogue Input 0 to 10V 0 to 100 Current Input Impedance 100k 0hm WARNING This is a non isolated product The control connections are not isolated from the AC supply Any...

Page 14: ...ture Output Positive Grd Protective Earth Ground Drive Module Protective Earth Ground Grd Protective Earth Ground Motor Protective Earth Ground Auxiliary Terminals The power must be supplied from an independent power supply which is not earth ground referenced Terminal Function Description Notes A1 Auxiliary Supply Auxiliary Relay Supply 16V at 10mA A2 0V Signal Common Signal Reference Must not be...

Page 15: ...to increase time P2 RAMP DOWN Setpoint ramp adjustment clockwise to increase time P3 SPEED STABILITY Speed loop stability clockwise increase response P4 CURRENT CALIBRATION Output current calibration clockwise to increase output P5 IR COMPENSATION Speed droop compensation armature voltage feedback P6 MINIMUM SPEED Clockwise to increase compensation Minimum speed at zero setpoint Can also be used a...

Page 16: ...3 4 Terminal Description 506 507 508 HA389427 ...

Page 17: ... than live and netral Run connects to Common to Enable Speed Control Current Control Figure 4 2 Wiring Diagram Current Control MAINS FILTER L1 L2 N GRD Fuse 6 5 4 3 2 1 10K I LIMIT 10 V SETPOINT RUN COMMON TACHO GENERATOR F F A A GRD FF F A AA T6 Fuse RUN neutral 10K SPEED SETPOINT Double reinforced insolation boundary provided by users potentiometers and run switch Optional Speed Setpoint potenti...

Page 18: ...Rating SSD Drives Fuse Isolator Kit Part Numbers 506 3A DC Armature AC Supply Ground 1 5mm2 16AWG 10A LA054664 507 6A AC Supply Ground DC Armature 2 5mm2 14AWG 1 5mm2 16AWG 10A LA054664 508 12A AC Supply DC Armature Ground 6 0mm2 10AWG 4 0mm2 12AWG 20A LA050062 Terminal Tightening Torques Terminal Torque Setting Power 0 8 Nm 7 lbf in Control 0 56 Nm 5 lbf in Ferraz Semiconductor Fuses Fuse Rating ...

Page 19: ...efer to the semiconductor fuses table on the previous page for recommended semiconductor fuse manufacturer and type number Short Circuit Rating The 506 and 507 controllers are suitable for use on a circuit capable of delivering not more than 1000 RMS symmetrical amperes 240V maximum whilst the 508 controller is suitable for use on a circuit capable of delivering not more than 5000 rms symmetrical ...

Page 20: ...CURRENT LOOP PI FIRING CIRCUIT CURRENT SCALING SW1 CALIBRATED ARMATURE CURRENT SPEED RANGE SCALE ARM VOLTAGE TACHO FILTER TACHO SW3 SW4 ARMATURE VOLTAGE FILTER BLOCK DIAGRAM 506 507 508 100 CURRENT CLAMP SPEED LOOP PI P3 STAB P5 IR COMP LINEAR RAMP UP RATE P1 DOWN RATE P2 TORQUE CURRENT LIMIT 10V 100 HEALTH LED 2 HEALTH SETPOINT SCALE SW2 I limit 0v 16V A1 20 2 P7 MAXSPEED A6 AUXILIARY SETPOINT MI...

Page 21: ...grounding terminals are identified with the International Grounding Symbol IEC Publication 417 Symbol 5019 Fitting Figure 4 3 Product Mechanical Arrangement Allow 50mm above and below product for cooling Allow 8cm access to one side of the unit Mount the unit with the cover in place DIN RAIL MOUNTING PANEL Mounting clip can be easily pushed to allow different mounting configurations USE M4 FIXINGS...

Page 22: ...05 mm 105 mm 105 mm E 50 mm 50 mm 50 mm F 140 mm 140 mm 140 mm Removing the Cover WARNING Isolate the controller before fitting or removing the cover Remove the cover to access the terminals and switches It is removed easily when the unit is mounted on the backplate There are no screw fixings It snaps back on to the front of the drive 8cm ...

Page 23: ...nce 4mm 12AWG Cable Terminals Suitable for 2 PE 200mm Flying Leads 2 G F H B E C D A 4 x M5 Inserts for DIN Rail Mounting at chosen height END USER TO AFFIX OWN DIN RAIL HERE TO MOUNT DRIVE 506 507 508 Filter Watt Loss Overall Dimensions Fixing Centres A B C D E F G H CO389115 9 5W 100 159 55 84 147 135 63 78 Note Note Watt Loss value is at a current output of 12 Amps dc ...

Page 24: ...and Set Up Warning Before applying power check Switch Selection a Mains switch set to intended supply voltage Left 110 120 Right 220 240 b Personality switches SW1 OFF ON 506 0 25 to 3A 0 5 to 3A 507 0 5 to 3A 1 to 6A 508 1 to 6A 2 to 12A Speed Range Maximum Feedback Voltage Range SW2 SW3 Armature or Tacho OFF OFF 15 to 30 ON OFF 30 to 60 OFF ON 60 to 120 ON ON 120 to 180 SW4 OFF ON FEEDBACK TACH ...

Page 25: ...Anti clockwise P7 Max Speed Mid b External Speed setpoint to minimum Motor a Check motor is compatible with controller and settings b Check motor and load are free to rotate Wiring a Check there is no loose wire ends on the PCB b Check that there are no free wire ends on external controls liable to contact grounded metal or earth ground referenced parts Applying Power 1 Power on LED 1 should illum...

Page 26: ...t to maximum and check armature voltage does not exceed rated value adjust maximum speed using P7 If a minimum speed setting is required reduce speed setpoint potentiometer to zero adjust minimum speed potentiometer P6 to give required value With speed setpoint at maximum re adjust maximum speed with P7 4 Adjust I Limit potentiometer to suit Motor Current Rating 508 506 507 0 5 1 1 5 3 2 1 3 5 4 2...

Page 27: ...ve and replace tacho Motor rotates in the wrong direction Speed is controlled though Motor connections are wrong for required direction with 1 Armature voltage feedback 2 Tacho generator Power off and reverse armature connections Power off and reverse both armature and tacho connections Motor will not turn and the stall light comes on after 15 seconds in speed control mode Motor shaft locked or ja...

Page 28: ...d Set up chapter Stall light comes on after 15 seconds in current control mode Incorrect wiring of run contact Run contact should be wired between the two terminals marked run and 10V Stall light comes on immediately after the run contact is closed Faulty or incorrect load across the A and A terminals Check motor armature thoroughly The Controller should not be used on motors with a low inductance...

Page 29: ...4 14 Installing the 506 507 508 506 507 508 HA389427 ...

Page 30: ...IT RETURN IT TO PARKER SSD DRIVES Returning the Unit to Parker SSD Drives Please have the following information available The model and serial number see the unit s rating label Details of the fault Contact your nearest Parker SSD Drives Service Centre to arrange return of the item You will be given a Returned Material Authorisation Use this as a reference on all paperwork you return with the faul...

Page 31: ...5 2 Routine Maintenance and Repair 506 507 508 HA389427 ...

Page 32: ...CE WITH THE EMC DIRECT IVE EMC INST ALLAT ION GUIDELINES STAT ED IN MANUAL CEMEP VALIDIT Y FIELDS 2 3 AND 4 NO EMC CE MARK APPLIED TO SSD MODULE A GLOBAL EMC SOLUTION MAY BE ADVANTAGEOUS MANUFACT URER SUPPLIER INST ALLERS RESPONSIBILITY T O CONFORM WIT H EMC DIRECTIVE SSD EMC CHARACTERISTICS AND MANUFACT URERS IN T HE OVERALL PRODUCT JUSTIFICATION RELEVANT APPARATUS T HE SSD MANUFACT URERS DECLARA...

Page 33: ...r EMC compliance when the unit is used as a component We Parker SSD Drives address as below declare under our sole responsibility that the above Electronic Products when installed and operated with reference to the instructions in the Product Manual provided with each piece of equipment is in accordance with the relevant clauses from the following standard BSEN61800 3 2004 The above Electronic Pro...

Page 34: ... Type of controller 15 maximum 20 typical Variable proportional plus integral s Feedback method 1 Va Tacho 0 100 load regulation Max torque speed range 2 2 typically 20 1 0 1 typically 100 1 3 Current Torque Control 1 Range selected by built in switches 2 Suitable for armature time constants not less than 5ms 3 All control terminals are at a potential of the peak of the input supply with respect t...

Page 35: ... s Environmental Requirements Operating Temperature 0 to 40o C Derate 1 5 Degree above 40o C Max Operating Temperature 50o C Humidity 85 R H at 40o C non condensing Altitude Above 1000m derate at 1 100m Atmosphere Non flammable non corrosive and dust free Storage Temperature Range 25o C to 55o C Transport Temperature Range 25o C to 55o C Enclosure IP2X suitable for cubicle mounting Installation Ca...

Page 36: ...95 2kV Self Recovery and EN50082 Signal Control Fast Transient Burst BS EN61000 4 4 1995 2kV Self Recovery 2 1995 Power Interfaces Fast Transient Burst BS EN61000 4 4 1995 2kV Self Recovery Emissions These levels of performance are achieved when installed as specified with the recommended Supply Filter Achieved with up to 50m of motor cable Port Phenomenon Test Standard Level Generic Standard Encl...

Page 37: ...A Typical Motor Horsepower Hp 90V Armature 110 120V AC 180V Armature 220 240V AC 1 10 1 6 1 6 1 3 1 6 1 3 1 3 3 4 1 3 3 4 3 4 2 Typical Motor Power kW 90V Armature 110 120V AC 180V Armature 220 240V AC 0 07 0 125 0 125 0 25 0 125 0 25 0 25 0 55 0 25 0 55 0 55 1 5 Controller loss W 5 10 10 20 20 40 Maximum AC Supply Current ls A rms 3 4 5 6 9 12 18 Maximum l2t for fusing A2s 36 36 80 80 365 365 Max...

Page 38: ...6 507 508 HA389427 Product Code Block Product Code Feature 1 Basic Product 506 3 Amp 507 6 Amp 508 12 Amp 2 Livery 00 Standard 01 to 99 Customer 3 Cover 20 IP20 Cover 4 Special Options 00 Standard 01 to 99 Documented Special Options ...

Page 39: ...178 1998 and updated EC Declaration of Conformity 13114 Removed address list from inside manual to back cover 13164 01 03 99 FEP GDR 8 Company name change 18354 19 07 05 CM GDR Certificate updated on page 6 2 9 Cover removal improved page 4 8 19650 17 10 06 CM GDR 10 Ambient temperature amended New company name 20002 19591 20 06 07 CM GDR FIRST USED ON MODIFICATION RECORD 506 507 508 Product Manua...