Identify and eliminate faults
BSP-MT 10-95/D3
41
Fault
Possible cause
Remedy
Specialised
personnel
Service
technician
Dryer does not switch
over
Solenoid valve Y1/Y2 does
not open correctly.
Check supply voltage, ca-
ble, contacts and solenoid;
replace, if necessary.
•
•
Solenoid valve Y1/Y2 can-
not be opened properly
(audible humming sound or
valve fl apping).
Check supply voltage.
Check pilot valves; replace,
if necessary.
•
•
Control board defective.
Check fuse in supply line
and in the switchbox; re-
place, if necessary.
•
•
Power supply interrupted,
cable broken.
Reconnect the unit to the
power supply.
•
•
Compressor might be off.
Check compressor synchro-
nisation circuit.
•
Error in control programme. Restart programme.
•
No expansion
Solenoid valve Y3/Y4 can-
not be opened.
Check supply voltage, ca-
ble, contacts and solenoid;
replace, if necessary.
•
•
Solenoid valve Y3/Y4 can-
not be opened properly
(audible humming sound or
valve fl apping).
Check supply voltage.
Check spring and solenoid;
replace, if necessary. Check
solenoid valve for contam-
ination; clean or replace, if
necessary.
•
•
Dryer is continuously
bled
Solenoid valve Y3/Y4
cannot be closed properly
(audible humming sound or
valve fl apping).
Check supply voltage.
Check spring and solenoid;
replace, if necessary. Check
diaphragm; replace, if
necessary.
•
•
Main valve V1/V2 does not
open.
Check main valve, replace
if nec.
•
•
Dryer is excessively
bled
Solenoid valve Y1/Y2 can-
not be closed
Check solenoid and
diaphragm; replace, if
necessary.
•
•
Pressure dew point is
not reached
Operating pressure is too
low.
Increase operating pressure.
•
Compressed air volume fl ow
is too high.
Reduce compressed air
volume fl ow
•