5 Control
QS
Main power switch
UP button: press to increase the value of a selected parameter
DOWN button: press to reduce the value of a selected param-
eter, press for more seconds to force the drain to work.
esc
ESC button :returns to the previous level
set
SET button : one single press to see the alarms, press for more
seconds to ON/OFF the dryer
(illuminated) Dew point correct
(Flashing) warning dew point high/low
(off) alarm dew point
(illuminated) Condensate drain ON
(off) Condensate drain OFF
(illuminated) Dryer ON
(off) Dryer OFF / Dryer stand by
(illuminated) with compressor OFF
(illuminated) Allarm
(Led illuminated
) Maintenance
°C
°F
(Led illuminated
) Grade
Bar
PSI
(Led illuminated
) Pressure
5.1 Parameter settings
There are two levels of protection for parameters:
a) User (U): with immediate access,
User-changeable;
b) Password protected Factory/Service (F/S): password required for ac-
cess;
Factory/Service use only.
5.2 Condensate drain
Ii is possible to modify the operating modes of the drain, using the
“TIME” menu.
There are two operating modes:
a) TIMED (CHd = ON) - with draining at intervals and settable time;
in this confi guration keep pressed
to force the drain to work;
b) EXTERN (CHd = OFF) - if there is an external drain.
Parameter table “TIME”
Code Defi nition
Default
Min
Max.
dON
Time ON Drain
5
1
60
dOFF
Time OFF Drain
120
20
2700
CHd
Confi guration drain
OFF
ON
OFF
For choosing the set proceed as follows (or see the fl ow chart):
Press buttons
set
and
esc
together over 5 seconds to enter on sub-
menu.
Using buttons
and
select “Par” and press
set
to confi rm.
Using buttons
and
select “TIME” and press
set
to confi rm.
Using buttons
and
select the code to change and press
set
to confi rm.
Using buttons
and
change the value and press
set
to confi rm.
Press
esc
to exit.
In the same way it is possible to change interval and discharge times of
the drain.
5.3 Software menu
It is possible to see the software version and set the dryer for the remote
control or the supervisor in the menu “CF9”.
Parameter table “CF9”
Code Defi nition
Default
Min
Max.
VER
Software Version
1.0
---
---
SOFt
Software type
1
---
---
rE
On/Off remote
(Table 1)
0
0
2
SUP
ON/OFF supervisor (Modbus)
OFF
OFF
ON
Table 1
On/Off remote mode
0
On/Off remoto disable
1
On/Off remote enable, local On/Off enable
2
On/Off remote enable, local On/Off disable
For choosing the set proceed as follows (or see the fl ow chart):
Press buttons
set
and
esc
together to enter on submenu.
Using buttons
and
select “Par” and press
set
to confi rm.
Using buttons
and
select “CF9” and press
set
to confi rm.
Using buttons
and
select the code to change and press
set
to confi rm.
Using buttons
and
change the value and press
set
to confi rm.
Press
esc
to exit.
Summary of Contents for StarlettePlus-ES Series
Page 2: ......
Page 106: ...8 5 EXPLODED DRAWING 8 SPE026 100 ES...
Page 110: ...8 8 WIRING DIAGRAM 12 SPE026 100 ES 70...
Page 111: ...8 8 WIRING DIAGRAM 13 SPE026 100 ES 026 040 156 240 026 040 312 600...
Page 112: ...8 8 WIRING DIAGRAM 14 SPE026 100 ES...
Page 113: ...8 8 WIRING DIAGRAM 15 SPE026 100 ES...
Page 128: ...RU 8 8 C M R www polewr com 2 o 1 a e Parker b Quasar LCD c d e f g 8 8 1 2 3 4 5 a b...
Page 129: ...13 196 2003...
Page 131: ......
Page 132: ......
Page 133: ......