English
3/6
PSH120-1200
• Avoid air inlet temperature fl uctuations.
4.4 Stop
a) Stop the dryer 2 minutes after the air compressor stops or in any
case after interruption of the air fl ow;
b) make sure compressed air does not enter the dryer when the dryer is
disconnected or if an alarm occurs.
c) Press
x
: the POWER LED (2) turns yellow again;
d) Turn the MAIN SWITCH “
&
” to “O OFF” to switch the power off.
Y
Wc version, close the water circuit with the dryer stopped.
5 Control
5.1 Control panel
4
5
2
1
3
y
x
é
z
è
[
&
Display
Reference
Name
Description
1
MAIN SWITCH
I ON = dryer powered;
O OFF = dryer not powered.
2
POWER LED
Yellow = dryer powered.
Green = dryer operating.
3
ENERGY SAVING
LED
Lit = dryer in energy saving con-
dition.
4
WARNING LED
Off = no signal.
Flashing = alarm or warning.
5
DRAIN LED
Lit = drain open.
Keypad mode
STANDARD
MENU*
x
ON/OFF BUTTON
Switching on/off
Confi rm
z
RESET BUTTON
Reset alarm/ warning
Up
é
HISTORY BUTTON
Alarm/warning log
Down
y
DRAIN BUTTON
Condensate drain
Out
* returns to STANDARD mode after 5 minutes.
5.2 Operation
Operation status
With the MAIN SWITCH “
&
” turned to “I ON” (dryer powered)
three working conditions are possible::
DRYER
STATUS
[
DISPLAY
POWER LED
(2)
1
OFF
Off
Yellow
2
ON
Dew point
Green
3
REMOTE OFF
r.OF
Yellow
To switch from OFF to ON (and vice versa) press
x
.
!
In OFF status the unit remains powered until the MAIN SWITCH“
&
” is turned to “O OFF”!
Y
To manage REMOTE OFF mode, remove the bridge between ter-
minals X4.0 and X4.10 (see par. 8.8) and connect the remote start/stop
switch (to be provided for by the customer).
In ON status, use the button with the following logic:
X4.0 X4.10
X4.0 X4.10
DRYER STATUS
ON
REMOTE OFF
!
Do not activate ON status (refrigeration compressor operating) more
than 10 times in one hour.
Scheduled maintenance
Y
When the DISPLAY
[
alternatively shows the
Sr
warning code
and dew point, contact authorized assistance personnel for carrying out
scheduled maintenance indicated in par. 6.3 and for resetting the warn-
ing code (see par. 5.4 in List of alarm/warnings).
Press
z
to cancel the warning for 24 hours.
Condensate drain
The drain works in TIMES mode, draining at set intervals (parameters d1,
d2; see par. 5.3).
Alarm log
Contains the descriptions of the last alarms (max. 8).
Press
é
for 5 seconds: the keypad now operates in Alarm
MENU mode and the events can be scrolled with
z
and
é
.
Every event is displayed with “ALx” (x=1-8).
AL1 = most recent event.
If there are no events “---” appears.
To view the details of the event, press
x
:
ALx
1 Alarm code
2 Thousands of hours
3 Hours
4 Dew point
5 Evaporation temperature
6 Compressor discharge temperature
Scroll with
z
and
é
.
Summary of Contents for Polestar-HP Smart PSH1000
Page 2: ......
Page 110: ...8 5 EXPLODED DRAWING 12 PSH120 1200 A B E D C 12 15 B3 4 5 1 8 3 9 2 B1 34 PSH 120 230 Ac ...
Page 114: ...8 5 EXPLODED DRAWING 16 PSH120 1200 34 15 9 B3 B E D C A 2 8 1 4 4 5 5 F G 22 B1 PSH 460 Wc ...
Page 117: ...8 6 DIMENSIONAL DRAWING 19 PSH120 1200 PSH 120 230 Ac ...
Page 118: ...8 6 DIMENSIONAL DRAWING 20 PSH120 1200 PSH 290 460 Ac ...
Page 119: ...8 6 DIMENSIONAL DRAWING 21 PSH120 1200 PSH 630 1200 Ac ...
Page 120: ...8 6 DIMENSIONAL DRAWING 22 PSH120 1200 PSH 290 460 Wc ...
Page 121: ...8 7 REFRIGERANT CIRCUIT 23 PSH120 1200 PSH 630 1200 Wc ...
Page 122: ...8 7 REFRIGERANT CIRCUIT 24 PSH120 1200 PSH 120 230 Ac ...
Page 123: ...8 7 REFRIGERANT CIRCUIT 25 PSH120 1200 PSH 290 460 Ac ...
Page 124: ...8 7 REFRIGERANT CIRCUIT 26 PSH120 1200 PSH 630 Ac ...
Page 125: ...8 7 REFRIGERANT CIRCUIT 27 PSH120 1200 PSH 800 1200 Ac ...
Page 126: ...8 7 REFRIGERANT CIRCUIT 28 PSH120 1200 PSH 490 460 Wc ...
Page 127: ...8 7 REFRIGERANT CIRCUIT 29 PSH120 1200 PSH 630 Wc ...
Page 128: ...8 7 REFRIGERANT CIRCUIT 30 PSH120 1200 PSH 800 1200 Wc ...
Page 129: ...8 8 WIRING DIAGRAM 31 PSH120 1200 Sheet 1 of 6 PSH 120 230 Ac ...
Page 130: ...8 8 WIRING DIAGRAM 32 PSH120 1200 Sheet 2 of 6 PSH 120 230 Ac ...
Page 131: ...8 8 WIRING DIAGRAM 33 PSH120 1200 Sheet 3 of 6 PSH 120 230 Ac ...
Page 132: ...8 8 WIRING DIAGRAM 34 PSH120 1200 Sheet 4 of 6 PSH 120 230 Ac ...
Page 133: ...8 8 WIRING DIAGRAM 35 PSH120 1200 Sheet 5 of 6 PSH 120 230 Ac ...
Page 134: ...8 8 WIRING DIAGRAM 36 PSH120 1200 Sheet 6 of 6 PSH 120 230 Ac ...
Page 135: ...8 8 WIRING DIAGRAM 37 PSH120 1200 Sheet 1 of 6 PSH 290 460 Ac Wc ...
Page 138: ...8 8 WIRING DIAGRAM 40 PSH120 1200 Sheet 4 of 6 PSH 290 460 Ac Wc ...
Page 139: ...8 8 WIRING DIAGRAM 41 PSH120 1200 Sheet 5 of 6 PSH 290 460 Ac Wc ...
Page 140: ...8 8 WIRING DIAGRAM 42 PSH120 1200 Sheet 6 of 6 PSH 290 460 Ac Wc ...
Page 141: ...8 8 WIRING DIAGRAM 43 PSH120 1200 Sheet 1 of 6 PSH 630 Ac Wc ...
Page 144: ...8 8 WIRING DIAGRAM 46 PSH120 1200 Sheet 4 of 6 PSH 630 Ac Wc ...
Page 145: ...8 8 WIRING DIAGRAM 47 PSH120 1200 Sheet 5 of 6 PSH 630 Ac Wc ...
Page 146: ...8 8 WIRING DIAGRAM 48 PSH120 1200 Sheet 6 of 6 PSH 630 Ac Wc ...
Page 147: ...8 8 WIRING DIAGRAM 49 PSH120 1200 Sheet 1 of 6 PSH 800 1200 PSH 800 1200 Ac Wc ...
Page 148: ...8 8 WIRING DIAGRAM 50 PSH120 1200 Sheet 2 of 6 PSH 800 1200 Ac Wc ...
Page 149: ...8 8 WIRING DIAGRAM 51 PSH120 1200 Sheet 3 of 6 PSH 800 1200 Ac Wc ...
Page 150: ...8 8 WIRING DIAGRAM 52 PSH120 1200 Sheet 4 of 6 PSH 800 1200 Ac Wc ...
Page 151: ...8 8 WIRING DIAGRAM 53 PSH120 1200 Sheet 5 of 6 PSH 800 1200 Ac Wc ...
Page 152: ...8 8 WIRING DIAGRAM 54 PSH120 1200 Sheet 6 of 6 PSH 800 1200 Ac Wc ...
Page 153: ......