Hyperchill-Precision Control HLS022-057
0
Relay normally deactivated, excited by an alarm.
1
Relay normally excited (also with control OFF), deactivated
by an alarm.
2
Relay normally excited (only with control ON), deactivated
by an alarm or with control OFF.
4.4.2 Temperature
control
PARAMETER
CODE
TYPE
DEFAULT
Temperature control set point
SEt
D
20.0
Set point lower limit
LI5
U
5.0
4.4.3
B1 sensor parameters
PARAMETER
CODE
TYPE DEFAULT
High temperature confi guration
cHAI
U
0
High temperature alarm
HAI
D
60.0
Low temperature alarm
LAI
D
-20.0
Alarm management
cLAI
U
1.0
Sensor calibration
CAI
U
0.0
Low temperature alarm reset
diff erential
dbI
U
1.0
4.4.4
B2 sensor parameters
PARAMETER
CODE
TYPE DEFAULT
High temperature confi guration
cHA2
U
0
High temperature alarm
HA2
U
60.0
Low temperature alarm
LA2
U
3.0
Sensor calibration
CA2
U
0.0
4.4.5
B3 sensors parameters
PARAMETER
CODE
TYPE DEFAULT
High temperature alarm
HA3
U
60.0
Low temperature alarm
LA3
U
-20.0
Sensor calibration
CA3
U
0.0
4.4.6 Compressor
parameters
PARAMETER
CODE
TYPE
DEFAULT
Compressor operation hour counter
HI
D
-
Compressor hour counter threshold
tHI
U
0
4.4.7 Pump
parameters
PARAMETER
CODE
TYPE
DEFAULT
Pump stop delay
dP5
U
5
Pump start delay
dPA
U
5
4.4.8
Antifreeze heater parameters
PARAMETER
CODE
TYPE
DEFAULT
Set point adjustment (B1)
SEA
U
19.0
Temperature control diff erential
(B1)
dIA
U
1.0
Antifreeze heater operating mode
(see para. 4.4.8.1)
FUA
U
2
Antifreeze heater activation mode
(see para. 4.4.8.2)
AbrA
U
2
Activation set point (B3)
ArA
U
5.0
4.4.8.1
FUA antifreeze heater operating mode
0
Heating element thermostatting by B1 with SEAsetting,
pump activation by B3 (ambient sensor) with ARA setting,
heating element activated if pump is activated.
1
Heating element thermost pump activation by B3
(ambient sensor) with ARA setting.
2
Heating element thermostatting by B1 with SEAsetting,
pump activation by B3 (ambient sensor) with ARA setting,
heating element and pump with separate activation.
4.4.8.2
AbrA antifreeze heater activation mode
0
Activation only when controller is ‘On’
1
Activation also when controller is ‘Off ’
2
Activation also when controller is ‘Off ’. During heater op-
eration the pump is activated.
4.5 Parameter management
4.5.1
Temperature setting (see fi g.1)
1. 1. Turn the main swicth (QS) to “ON” and wait for the temperature
visualization.
2. Press buttons “
P3
” and “
P5
” together, to enter into “
dIrE
” (D)
parameters.
3. Press button “
P4
” to select “
SEt
” parameter, press the button
“
P5
” to confi rm.
4. Change the value, using the up and down arrow buttons “
P3
” and
“
P4
”, then press button “
P5
” to confi rm.
6. Press the button “
P3
” to return on “
dIrE
”
parameter.
7. Press the button “
P5
” to exit.
4.5.2
Visualization sensors B1,B2...
“B1” is the “set” sensor of the macchine.
1. Start the chiller.
2. Press the button “
P4
” to visualize the temperature of the next sen-
sor.
3. Press the button “
P5
” to visualize the sensors “
b01
” ..“
b02
”....
It is recommended to leave on the display the B1 “set” sensor.
4.6 Alarms management
4.6.1
Digital input alarms
ID
CODE LED
DESCRIPTION
RESET
ID1
HPI
L5
High pressure alarm from pressure
switch
M
ID2
LPI
L6
Low pressure alarm from pressure
switch
M
ID3
tP
L7
Pump thermal cutout alarm
M
ID4
LL
L8
Water tank low water level alarm / No
water fl ow
A
ID6
PII
L9
Compressor protection alarm /
Phases monitor
M
4.6.2
Allarmi da ingressi analogici
AI
CODE
DESCRIPTION
RESET
B1
HAI
Tank water outlet water high tempera-
ture alarm
Warning
LAI
Tank water outlet water low tempera-
ture alarm
A
StI
Sensor open circuit or short circuit
M
B2
HA2
Evaporator water outlet water high
temperature alarm
Warning
LA2
Evporator water outlet water low tem-
perature alarm
A
St2
Sensor open circuit or short circuit
M
B3
HA3
High ambient temperature warning
Warning
LA3
Low ambient temperature warning
Warning
St3
Sensor open circuit or short circuit
M
4.7 Automatic restart
In the event of a power failure, when power is restored the chiller will
assume theOn-Off statusheld at themoment the power was lost.
Summary of Contents for Hyperchill HLS022
Page 2: ......
Page 10: ...Italiano 8 8 Hyperchill Precision Control HLS022 057 ...
Page 18: ...English 8 8 Hyperchill Precision Control HLS022 057 ...
Page 26: ...Español 8 8 Hyperchill Precision Control HLS022 057 ...
Page 34: ...Deutsch 8 8 Hyperchill Precision Control HLS022 057 ...
Page 35: ......