Notices for Safety

2

1. Install 

1) Before installing this machine, install main power circuit breaker (NFB) and Magnetic switch on the outside of the

main body for safety.

2) If, after transport or storage in humid conditions, equipment could fail to meet all the safety  requirement, the install 

instruction shall 4 hour of operation to dry out the equipment and  restore it to normal condition.

2.  Ground type 1 grounding or special type 3 grounding in the exterior box of the machine to prevent  electric shock.
3.  Check that voltage of provided power is same as the voltage of the machine and the rated current is not exceeding 

proper capacity of load current.  Then, provide the power.

(It is recommended that you do not use a machine at over 70% of the rated current condition.)

4.  Fuse

1) To prevent fire and to protect the machine, use a fast-acting fuse, which is designated by our company. 

(Refer to the product label )

2) Must turn off the main power to exchange the fuse. 
3) The fuse used must be of the specified rating (current, voltage, type) in order to prevent a fire hazard.   

5.  Environments 

1) Adjust ventilation and temperature so that temperature inside the control panel is not over 45

˚C.

2) Do not operate the machine where there is a risk of inflammability, explosiveness, corrosion or humidity. 

(RH 70% below at 40

)

3) The equipment must not be mounted on a surface of flammable material.
4) Live parts may need to be accessible, a statement requiring the fitting of a residual current-opened circuit-breaker. 

6.  Disassembly or remodeling of the machine

1) Never change components voluntarily with the exception of changes of fuse or thyristor.
2) Our company can not guarantee operation of the machine when the volume of the machine or component is altered 

voluntarily.  When a problem occurs, please contact our company’s A/S Department.

7.  Check and repair

1) Before checking the machine, cut off the power and beware of electric shock.
2) Check fastening condition of bolts and nuts of terminal parts.
3) When bolts of terminal are loose, it could generate heat so wiring can be damaged or fire can occur.  

Check this condition periodically.

8.  This manual could be revised without notification for improvements of functions of the machine.
9.  Responsibilities and guarantee

1) Must preserve notices for handling, maintenance, and repair of the machine.
2) Our company is not responsible for damage, which occurs due to not following these instructions.

10. Cleaning

1) Do not spray water directly at the product. (A fire and electric shock will be occurred)
2) Please unplug the product
3) Do not use chemical liquid. Discoloration will be occurred.
4) Appropriate decontamination is carried out if hazardous material is split onto or into the equipment.
5) Cleaning and decontamination necessary as a safeguard when laboratory heating equipment and any accessories are 

maintained, required and transferred.

11. Protection against electric shock

1) The hazardous live parts are supplied from a circuit protected by a residual current operated circuit-breaker which 

interrupts the supply at a differential current of 30mA or less, or the installation such a circuit-breaker.

2) Conveyor belts, muffles, etc. which are conductive are connected to the protective conductor terminal.
3) Please express clearly the necessary method to be carried for protection and method for protection on where operator 

or other personnel can be contacted such as rechargeable part or terminal connected to conductive circuit.
(ex. Isolation tools, isolation cable)  

12. A/S Request

A/S Department

TEL  (031) 831 – 8310~8312
FAX  (031) 831 – 8314
Mail : [email protected]
Homepage : www.paratec.co.kr

Summary of Contents for TE Series

Page 1: ...USER S MANUAL TE TYPE VER 1 00...

Page 2: ...achine or component is altered voluntarily When a problem occurs please contact our company s A S Department 7 Check and repair 1 Before checking the machine cut off the power and beware of electric s...

Page 3: ...Product Model E E TYPE 3 Rated Voltage 1 110V 2 220V 3 380V 4 440V 4 Rated Current 25A 70A 5 OPTION F With Fuse Blank Without Fuse 6 OPTION FN With Cooling Fan Blank Without Cooling Fan T E 2 0 2 5 F...

Page 4: ...Transformer coupled load Zero Crossing Resistive load only Minimum Load 1A Control Input Auto 4 20mA Default 0 20mA 0 5VDC 1 5VDC 0 10VDC Option Manual Outer 10K potentiometer Selecting Method Selecti...

Page 5: ...inside of panel 3 Fasten the mounting bolt NO 8 in name of each part tightly 4 2 1 VENTILATIO AND COOLING 1 This product is cooled by nature and by cooling fan 55 70A Basically with cooling fan 2 In c...

Page 6: ...t signal Connect mechanic relay no voltage onto Run Stop Alarm relay is N O Normal open 6 3 OUTPUT VOLUME DIP SWITCH 3 OFF Using inner volume on page 5 ON Using manual volume of 10k 6 4 SELECTING CONT...

Page 7: ...dip switch should be on to adjust inner output volume Please check it out for proper use before operation You can not use manual input 10K and outer output volume 10K together 7 4 ADJUSTING OUTPUT VOL...

Page 8: ...n each phase is less than 1A Or when fuse is burnt Blink Failure of SCR When input signal is 0 and output current on each phase is more than 1A Blink Over Current Output current is more than 120 than...